5
PARAMETER ADJUSTMENT
Vmax.OP
(Trimmer TM1) adjusts the maximum
speed when opening
Power.OP
Power.CL
Braking.OP
Braking.CL
Vmax.OP
Maximum opening speed
60 %
Vmin.OP
adjusts the minimum opening speed
Vmax.CL
(Trimmer TM2) adjusts the maximum
speed when closing
Vmin.CL
adjusts the minimum closing speed
Power.OP
adjusts the force when opening
Power.CL
adjusts the force when closing
Breaking.OP
sets the opening slowdown duration
Breaking.CL
sets the closing slowdown duration
TCA
adjusts the automatic closing time
TRA.OP
adjusts the leaf delay time in opening (for
double leaf MASTER/SLAVE)
TRA.CL
adjusts the leaf delay time in closing (for
double leaf MASTER/SLAVE)
To modify the value, use keys
+
(P1)
and
-
(P2).
To confirm use
(P4)
, to cancel
X (P3).
When changing one or more adjustments, it will be necessary to update the stroke
(see "Adjustments
Stroke update")
DIGITAL DIPSWITCH PROGRAMMING
The dipswitch status can be modified with the
(P1)
key. To confirm, use
(P4)
, to cancel
X (P3).
Dip05 EMERG_MD
Dip06 ELOCK_MD
Dip07 BATT_MD1
Dip08 BATT_MD2
Dip05 EMERG_MD
Operating emergency
input
ON
ON
OFF
OFF