13
G1 Encoder fault
motor 1
Encoder fault check
connections
Make sure that the motor is moving, that the
encoder connector is correctly inserted and
that its cable is not damaged.
G2 Motor 1 fault
Check motor
connections
Make sure that the operator is moving, that
its connector is correctly inserted and that its
cable is not damaged.
G3 Over Current
motor 1
motor absorption
exceeding the limits
The motor absorption exceeds the limits
set. Make sure that the installation is correct
from a mechanical point of view (smooth
run, weight and so on).
G4 Obstacle
detected by motor
encoder 1
Obstacle detected,
check the leaf sliding
and the encoder
functionality
If the problem persists, remove the obstacle
or check the sliding of the door. If necessary,
increase the force values with the parame-
ters Power.OP and Power.CL.
G5 Encoder fault
motor 2
Encoder fault check
connections
Make sure that the motor is moving, that the
encoder connector is correctly inserted and
that its cable is not damaged.
G6 Motor 2 fault
Check motor
connections
Make sure that the operator is moving, that
its connector is correctly inserted and that its
cable is not damaged.
G7 Over Current
motor 2
motor absorption
exceeding the limits
The motor absorption exceeds the limits
set. Make sure that the installation is correct
from a mechanical point of view (smooth
run, weight and so on).
G8 Obstacle
detected by motor
encoder 2
Obstacle detected,
check the leaf sliding
and the encoder
functionality
If the problem persists, remove the obstacle
or check the sliding of the door. If necessary,
increase the force values with the parame-
ters Power.OP and Power.CL.