Chapter 1 Checks and Adjustments
1-2
Commissioning Manual
308011En, Ed.2/Rev.B
June 2008
•
Check that the correct hardware parts are installed.
•
Make sure that you bring appropriate tools and instruments.
•
Install TankMaster.
1.3
Tank Interior Conditions
Look for objects which may produce disturbing echoes like girders,
heating coils or agitators. Disturbing objects can severely affect the
accuracy of the measurements.
1.4
System Composition
Enter the following information about the system:
•
Number of tanks.
•
System Master. There may be several units acting as master at
different occasions. The system is supervised by TankMaster
(WinOpi). A portable service PC may temporarily be connected to
an FCU when system service is required (WinSetup). A host com-
puter can be connected to an FCU or to the TankMaster PC in
order to further process measured data (level, temperature, pres-
sure etc.).
•
The number of FCUs, FBMs, RTGs and DAUs.
1.5
FCU checklist
1.5.1
FCU information
Note the name, Unit ID
and address of each FCU.
This will facilitate the
configuration of the Rex
system. Check that the
Unit ID placed at the cover
of the FCU box and on the
FCU motherboard match.
Note the address which
will be used for the
different FCUs.
1.5.2
Visual check
•
The FCU is not intrinsically safe. It must therefore be installed in a
nonhazardous area.
•
Weather protection: make a note whether the FCU is placed in a
control room or another weather protected location.
Figure 1-1. Position of Unit ID on FCU
cover.