1-19
Rosemount TankRadar Rex
Chapter 1 Checks and Adjustments
Commissioning Manual
308011En, Ed.2/Rev.B
June 2008
1.13 Rex Configuration
1.13.1
Tank Information
Check that the following items are correct in
TankMaster
:
•
Tank name.
•
Check that the Unit ID corresponds to the RTG installed at the cur-
rent tank.
•
RTG address corresponds to the address specified in TankMas-
ter.
To view the Unit
ID and RTG address
:
1
Select the Rex transmitter icon in the WinSetup workspace.
2
Click the right mouse button and choose the
Properties
option.
3
Select the
Communications
tab.
1.13.2
Tank Distances and RTG Geometry
Check that the following tank parameters are correct in
TankMaster
:
•
Tank Reference distance,
R
(
Holding register
1000).
•
RTG Reference distance,
G
(
Holding register
1002).
•
Calibration distance (
Holding register
1004).
•
Minimum Level distance,
C
(
Holding register
1006)
•
Hold off distance (
Holding register
1008)