1-7
Rosemount TankRadar Rex
Chapter 1 Checks and Adjustments
Commissioning Manual
308011En, Ed.2/Rev.B
June 2008
1.8.3
Tank measurements
•
Tank reference distance, R
. The R distance is defined as the dis-
tance between the
dipping datum point
(zero level) and the
tank
reference point
.
•
RTG reference distance, G
. G is the distance between the
tank
reference point
(hand dip nozzle) and the
RTG reference point
.
The RTG reference point is underneath the RTG flange, see Fig-
ure 1-5.
•
Minimum level distance, C
. C is the distance between the
dip-
ping datum point
(zero level) and the
bottom of the tank
.
•
Note the distance (mm) from max product level to RTG reference
point.
Note!
The G value is defined as positive if the Tank Reference point is located
above the RTG Reference point.
Figure 1-5
Tank distances.
Tank Reference Point
RTG Reference Point
Dipping Datum Point
(Zero Level)
Min. Level distance, C
RTG Ref.
distance, G
Ta
nk Refer
e
nce di
st
anc
e
, R
RTG Reference
Point