WATER SHUT-OFF DELAY ADJUSTMENT (SWITCHES 5 & 6)
The WaveCrest controller provides four periods to select
from for shutting off the water when the object is removed
from in front of the Sensor. The time periods to select from
are: 1 second, 10 seconds, 15 seconds, and 30 second.
The default setting is 1 second.
PERIOD
1 seconds
10 seconds
15 seconds
30 seconds
SW(5)
OFF
OFF
ON
ON
SW(6)
OFF
ON
OFF
ON
Water Shut Off Delay Selection
METERING MODE (SWITCH 7)
If metering mode is activated, every time the sensor is triggered, the water
will turn on and remain on continuously for 15 seconds. After that, the water
is turned off and the sensor will wait to be triggered again.
Metering Mode
SW (7)
ON - (Enable)
OFF - (Disable)
FEATURES
WATER FLOW CONTROL ADJUSTMENTS
The WaveCrest controller off ers a selection of pre-set
fl ow control adjustments. These selections are made
by confi guring a bank of seven switches, SW(1) to
SW(7), according to the tables below. The fl ow control
switches are located behind the battery cover just
above the batteries. Note SW(8) is not used.
PERIOD
15 seconds
30 seconds
45 seconds
60 seconds
3 minutes
20 minutes
SW(1)
OFF
OFF
OFF
OFF
ON
ON
SW(2)
OFF
OFF
ON
ON
OFF
OFF
SW(3)
OFF
ON
OFF
ON
OFF
ON
Auto Time Out Selection
AUTO TIME-OUT ADJUSTMENT (SWITCHES 1-3)
The WaveCrest controller provides six periods to select from for shutting off the water when the
object is left in the range triggering the Sensor. The time periods to select from are: 15 seconds,
30 seconds, 45 seconds, 60 seconds, 3 minutes
and 20 minutes. The default setting is
15 seconds.
Note:
The chart indicates the switch positions
required for each period of auto time-out.
AUTO-FLUSH (SWITCH 4)
The WaveCrest controller off ers the option to select the Auto Flush mode in
switch 4 position. When enabled, the controller will fl ush the faucet every
12 hours after the last use, for 30 seconds. Default setting from the factory is
in the “OFF” position.
Auto Flush Mode
SW (4)
ON - (Enable)
OFF - (Disable)