47
-
For the sake of flexibility, the Radiation sets enable dividing the 24 hours of the day
into three parts and each part may have its own definition of threshold and
minimal/maximal intervals.
The selection of the Radiation sensor to be referred to is done through an
auxiliary screen containing all the analog sensors and the user has to mark
the sensor to be used.
The purpose of defining the sensor’s coefficient is to
enable using the same sensor in different sets, but being able to refer to it
differently. The coefficient is expressed in %. When the coefficient equals 0
the radiation set is disabled.
Notice that:
The same
Radiation set
can be used by several irrigation programs.
10.
Filtration
The filtration program is defined per each filtration site independently. Each program
contains the
Interval
between the flushing cycles, the
flushing time
per station,
the
Dwell time
between the stations and in case there exists a Down Stream
(pressure sustaining) valve, the
Pre Dwell time
between the opening of the Down-
Stream valve and the first station.
Beginning and ending
of the 3 periods
The radiation
sensor to refer to
The radiation
sensor’s coefficient
Minimal and maximal
interval