![Taco 00e Series Скачать руководство пользователя страница 47](http://html2.mh-extra.com/html/taco/00e-series/00e-series_installation-operation-instruction-manual_3166579047.webp)
-47-
Address
Register name
Range
Resolution
Description
014
SET1Type
---
1
Configuration for SET1 terminal.
0 = “NO FUNCTION”
1 = “RUN input 2-3V”
2 = “MAX input 0-10V”
3 = “MAX input 2-10V”
4 = “RUN input 4-6mA”
5 = “MAX input 0-20mA”
6 = “MAX input 4-20mA”
7 = “FB output 10.5V”
8 = “FLOW output 2-10V”
9 = “FLOW output 4-20mA”
10 = “RPM output 2-10V”
11 = “RPM output 4-20mA”
12 = “ERROR output 10-0V”
13 = “ERROR output 20-0mA”
14 = “PWM SOLAR input”
15 = “PWM HEATING input”
16 = “PWM FLOW+ERR output”
015
SET2Type
---
1
Configuration for SET2 terminal.
See enumeration for register 014
016
SET3Type
---
1
Stop bits used for communication. 2 stop
bits will only be used when “Parity” is set to 0.
1 = 1 stop bit [default]
2 = 2 stop bits
017
Relay2Control
0..2
1
Configures module relay output.
0 = indicates fault
1 = indicates pump ready
2 = indicates pump operation
See section
“Error! Reference source not found. Error!
Reference source not found.”
VR status registers
Registers in this block are read with either function codes 0x03 or 0x04. They are read-only.
This block can be used for various kinds of fault finding.
Address
Register name
Resolution
Description
021..022
RESERVED
---
---
023
Software Version
0.1
Module software version
024..029
RESERVED
---
---
030
Product Version
1
Product version [32x for module, x denotes hardware revision]
031
RESERVED
---
---
032
Software Version
0.1
Module software version[10 = 1.0]
Содержание 00e Series
Страница 55: ...55 VR15 L M H VR20 L M H...