17.8 Analog Inputs (Object Type 0) • NOTE: Values are read-only
Instance Object Name
Unit
Description
AI.0
Actual Set Point
%
Currently active Setpoint
- 100% represents maximum
- Pump performance depending on Control Mode
- <0% indicates user control
AI.1
Actual Operating Mode
---
Current pump operating mode
- Mirrors AO.1 when remotely controlled
- See AO.1 for possible values
AI.2
Head
ft (H
2
O)
Estimated pump head
AI.3
Flow
GPM
Estimated flow
AI.4
Power
W
Electrical power of the pump
AI.5
Speed
RPM
Motor speed
AI.6
Motor Temperature
˚F
Medium or motor temperature
AI.7
Heatsink Temperature
˚F
Controller temperature
AI.8
HMax
ft (H
2
O)
Maximum pump head
AI.9
QMax
GPM
Maximum pump flow
AI.10
PMax
W
Rated pump power
AI.11
RPMMax
W
Maximum motor speed
AI.12
Operating Hours
h
Time active (not implemented = 0)
AI.13
Energy Consumed
kWh
Total electrical energy (not implemented = 0)
AI.14
Active Error Code
---
Currently active error.
0 = pump is operating without problems.
This value will always be non-zero when there is an error present.
(See section 19 “Error codes” for code details)
17.9 Analog Outputs (Object Type 1)
Instance Object Name
Unit
Description
AI.0
Bus Set Point
%
Currently active Setpoint
- 100% represents maximum
- 0% stops the pump
- Set B0.0 to enable
AI.1
Bus Operating Mode
---
Current pump operating mode
- 0: Auto mode (only on/off )
- 1: Proportional pressure, setpoint controls peak head
- 2: Constant pressure, setpoint controls head
- 3: Constant RPM, setpoint controls speed.
- Other values reserved
- Set B0.0 to enable