-35-
Pump Configuration: Using the drop down the pump settings can be changed
Op Mode: Changes to Operational Modes can be made using the dropdown (Off, Proportional &
Constant Pressure, Constant Speed or Combined Mode)
Max Head: Dropdown selects a specific maximum head (not applicable in Constant Speed Configuration).
This value is carried over to the max value in brackets on the Overview Tab
Max RPM: Dropdown sets the maximum speed. IMPORTANT NOTE: If an external speed control input used this
value must NOT be set a MAX. Max RPM shown on Overview page.
Qprop: Manually sets the slope of the proportional pressure curve
Night Mode: Toggles Night Setback on and off
Control Configuration: Ability to change the Mode, input, and output settings
Содержание 00e Series
Страница 55: ...55 VR15 L M H VR20 L M H...