16.1 Bus Topology
Figure 4: connecting to a computer with a standard cable
Figure 5: connecting to a network via router
16.2 Connection to a Pump Ad-Hoc
When connecting directly with the computer, a standard Ethernet cable must be used to connect with the
pump. The pump can then be accessed by typing IP address “192.168.0.245” or “00e” (or “192.168.0.246” or “00e2”
if it is a left twin pump) into your web browsers address bar.
16.3 Connection to a Pump via Router
When connecting via a router, Ethernet must be used to connect with the pump. The pump can then be
accessed by typing IP address “192.168.0.245” or “00e” or “192.168.0.246” or “00e2” if it’s a left twin pump in
to your web browser’s address bar.
16.4 Local Network Setup, Display & Diagnostics
For advanced setting options and troubleshooting data the pump operational data, settings, network settings, logging
of overload history, and software updates the pump controller can be accessed using the html web pages. Note:
• Connection to the internet is NOT required
• Standard or crossover ethernet cables, CAT 5 and above can be used. IMPORTANT: When connecting pump
to pump for parallel applications a crossover ethernet cable must be used.
• Due to the drive enclosure NEMA rating, a common RJ-45 ethernet network connector will not fit through
the drive opening. If the ethernet cable is intended to be a permanent installation it is recommended to
wire the cable end after the cable is fed through the opening in the drive enclosure.
• There are no additional devices or proprietary software required to access the pumps html web pages.
Modbus RTU over RS-485
VR Series is a Modbus RTU lag pump.
Typically, only one lead pump is connected to the serial bus, and one or several lags are also connected to the
bus. Lags do not communicate with each other and will never transmit data without receiving a proper request
from the master device.
Modbus over Ethernet
Modbus device is available at port 502. Default address is thus 192.168.0.245:502
Supported protocols are:
• Modbus TCP
• Modbus RTU over TCP
• Modbus UDP
• Modbus RTU over UDP
Protocol is automatically recognized according to received packet and no additional configuration is needed.