15. RELAY OUTPUT
Terminal Designation
Terminal description
MODE
Mode selection rotary switch. Used to show and configure mode of operation for relay.
LED1 / LINK
Slowly blinking when module is powered, permanently lid when link established
7
.
LED2 / ACT
Flashing yellow when data reception detected. Combined (OR)
with Modbus & BACnet data reception indication
7
.
NC
Normally closed relay contact. Opens when relay is active.
C
Relay common contact.
NO / OK
Normally open relay contact. Closes when relay is active.
NOTE: VR25-H, VR30-M and VR30-H have one status relay, used to signal pump operation or malfunction.
All other models have two relays. See table following for functionality.
The communications module has a built in web server which allows you to access your pump directly from an existing
Ethernet network. Direct connection to a computer is also possible with a crossover cable.
The web server uses HTML pages to set/view:
• Regulation mode settings
• Regulation parameters (power, RPM, head, flow, efficiency)
• Relay settings
• External control inputs
• Current and previews error
• Pump statistics (power consumption, run time and other).
7
When Mode 6 or Mode 7 is selected, LED1 and LED2 will show relay configuration. See section “4.3 Module mode selection”
LED is on
LED is off
16. NETWORK
Terminal Designation
Terminal description
MODE
Can be used to reset network configuration
LED1 / LINK
Slowly blinking when module is powered, permanently lid when link established.
Ethernet
10BASE-T RJ-45 connector.
LED2 / ACT
Indicates Ethernet activity or Modbus reception.
Relay
Configuration
Output
Status
Description
Relay
Position
LED status
7
LED 1 LED 2
0
Error
[default]
Only active when the pump is powered up and
detects a problem with operation.
1
Ready
The relay signal is active when the pump
is ready for operation.
2
Operation
The relay signal is active as long as the pump is operating. If the
pump comes to a stop or an error occurs, relay will deactivate.
---
---
Relay output not active.
Relay configuration number can be modified by either the web interface, Modbus register 012 (relay 1), 17 (relay 2 where applicable) or the Mode switch.