![Taco 00e Series Скачать руководство пользователя страница 18](http://html2.mh-extra.com/html/taco/00e-series/00e-series_installation-operation-instruction-manual_3166579018.webp)
-18-
13 Controller Layout
VR 25H, VR 30M and VR30H controller
Terminal Designation
Description
MODE
Mode selection rotary switch. Used to configure
mode of operation for the circuit. See section
14.3 “Module mode selection”
LED1 / LINK
Slowly blinking when module is powered.
Blinking fast when Modbus Error.
Permanently lid when Ethernet link established.
Ethernet
10BASE-T RJ-45 connector.
LED2 / ACT
Indicates Ethernet activity,
Modbus or BACnet activity.
B/D-
RS-485 negative data signal for
Modbus or BACnet.
A/D+
RS-485 positive data signal for
Modbus or BACnet
SET1 / RUN
Control signal 1.
COM / 0V
RS-485 common and analog input
common (ground).
SET2 / MAX
Control signal 2.
SET3 / FB
Control signal 3.
NC
Normally closed relay contact.
Opens when relay is active.
C
Relay common contact.
NO / NO
Normally open relay contact.
Closes when relay is active.
All models except VR25H, VR30M and VR30H
Analog Signals (SET1, SET2, SET3) • 12.5
Input Voltage Range
-1 to 32 VDC
When used as input.
Output Voltage Range
0 to 12 V
When used as output. 5 mA max. Load allowed per output.
Input Resistance
~100 k
W
0.5 mA load is added for most configurations.
---
---
Current sink to COM if configured as output.
Relay Specifications • 12.6
Connection Type
Screw-less terminals
Rating
- 250 VAC, 8A
Potential free changeover contact.
- 48VDC, Max Load up to 500VA
+
24
V
SET3
/ FB
SET2
/ MAX
COM
/
Ø
V
SET1
/ RUN
COM
/
Ø
V
B/D
-
A
/D +
NO
C
NC
GR
O
U
N
D
N
EUTRAL
LI
N
E
RS 485
ANALOG
RELAY
ETHERNET
LED1 LED2
L
N
Содержание 00e Series
Страница 55: ...55 VR15 L M H VR20 L M H...