English
24 TControl POD glass EC
Modbus Holding Register (R/W)
Address-H Min. Max. Gain Name
Description
EEPROM
73
0
50
0.1 Time slot 2 setpoint period 4
(#) Time slot 2 period 4
4
74
0
4
-
Time slot 2 AC fan period 4
(#) Time slot 2 period 4
4
75
0
1
-
Time slot 2 ECO mode period 4
(#) Time slot 2 period 4
4
76
-
-
-
Time slot 3 weekdays
(#) Time slot 3 weekdays
4
77
0
23
1
Time slot 3 start time period 1
(#) Time slot 3 period 1
4
78
0
59
1
Time slot 3 start minute period 1
(#) Time slot 3 period 1
4
79
0
50
0.1 Time slot 3 setpoint period 1
(#) Time slot 3 period 1
4
80
0
4
-
Time slot 3 AC fan period 1
(#) Time slot 3 period 1
4
81
0
1
-
Time slot 3 ECO mode period 1
(#) Time slot 3 period 1
4
82
0
23
1
Time slot 3 start time period 2
(#) Time slot 3 period 2
4
83
0
59
1
Time slot 3 start minute period 2
(#) Time slot 3 period 2
4
84
0
50
0.1 Time slot 3 setpoint period 2
(#) Time slot 3 period 2
4
85
0
4
-
Time slot 3 AC fan period 2
(#) Time slot 3 period 2
4
86
0
1
-
Time slot 3 ECO mode period 2
(#) Time slot 3 period 2
4
87
0
23
1
Time slot 3 start time period 3
(#) Time slot 3 period 3
4
88
0
59
1
Time slot 3 start minute period 3
(#) Time slot 3 period 3
4
89
0
50
0.1 Time slot 3 setpoint period 3
(#) Time slot 3 period 3
4
90
0
4
-
Time slot 3 AC fan period 3
(#) Time slot 3 period 3
4
91
0
1
-
Time slot 3 ECO mode period 3
(#) Time slot 3 period 3
4
92
0
23
1
Time slot 3 start time period 4
(#) Time slot 3 period 4
4
93
0
59
1
Time slot 3 start minute period 4
(#) Time slot 3 period 4
4
94
0
50
0.1 Time slot 3 setpoint period 4
(#) Time slot 3 period 4
4
95
0
4
-
Time slot 3 AC fan period 4
(#) Time slot 3 period 4
4
96
0
1
-
Time slot 3 ECO mode period 4
(#) Time slot 3 period 4
4
97
0
1
-
Daylight saving time
0: Deactivated (Factory setting)
1: Activated (CET)
4
98
0
2
-
Terminal unit assignment
0: Heat/Cold (Factory setting)
1: Heat
2: Cool
4
108
0
1
-
Heat control type
0: PI control (Factory setting)
1: 2-point control
4
109
0
1
-
Cold control type
0: PI control (Factory setting)
1: 2-point control
4
110
1
5
-
Ventilation stages
1: 1 Stage
2: 2 Stages
3: 3 Stages (Factory setting)
4: 4 Stages
5: 5 Stages
4
111
0
10
0.1 Min. ventilation value
0-100
≙
0-100% (0-10 V)
*
Factory setting: 0%
4
112
0
10
0.1 Max. ventilation value
0-100
≙
0-100% (0-10 V)
Factory setting: 100%
4
114
0
1
-
Setpoint change adjustment
0: Setpoint offset (Factory setting)
1: Setpoint
4
115
-
-
-
Special ON/OFF button function
0: No function (ON/OFF activated)
1: In-use switch
2: In-use
3: Not in-use
255 (=0xFF): On/Off button locked
4
124
0
1
-
Parameter menu locking
0: Free (Factory setting)
1: Locking
4
129
-1
20
1
Start with an adjusted variable > x
-1: Independent (factory setting)
0-20
≙
0%-20%: Dependent
4
130
0
2
-
Object status after voltage recovery
0: Standby
1: Last status of the object
2: ON (Factory setting)
4
131
0
1
-
Value status after voltage recovery
0: Last values (Factory setting)
1: Value reset
4
132
0
1
-
Heat output status (not with 3AO
variant)
0: NC (Factory setting)
1: NO
4
133
0
1
-
Cool output status (not with 3AO
variant)
0: NC (Factory setting)
1: NO
4
*
Содержание TControl POD glass EC