English
20 TControl POD glass EC
The active setpoint is determined by the time slot configuration. If no time slot is configured, the “setpoint
after power-up” parameter is used as a reference. The user can change the values within the defined limits.
Locally, it is possible to configure the setpoint as required. Supervision by Modbus also allows this.
After restarting the controller, this value (Refer to the §
, page 22 - address 20) is used
as setpoint until a new setpoint or setpoint via Modbus is activated.
12. SETPOINT
12.1. GENERAL
12.2. SETPOINT AFTER POWER-UP
12.3. NOT IN-USE SETPOINT OFFSET
A period is active if the start time and days match the programmed values. A period remains active until
the conditions of another period are met. The active setpoint can be overridden by Modbus via the basic
setpoint register (address 255).
Time slots have priority. Slot 3 has the highest priority.
A time slot is inactive if:
²
Time: 00:00
and
²
Fan speed: 0
and
²
Setpoint: 21.0°C
and
²
ECO: Off
13. REMINDER
, page 22 - address 135
When changing the in-use/not in-use mode, the setpoint offset by applying an offset (Refer to the §
, page 6) can be:
²
maintained (0)
the in-use/not in-use setpoints are changed with the same offset
²
reset (1)
The offset is reset for both setpoints
²
restored (2)
For the not in-use mode, no offset is applied to the setpoint In in-use mode the offset is applied to
the setpoint.