14 TControl POD glass EC
7.6. CONFIGURATION MENU
This menu allows you to configure a
TControl POD glass EC
according to 4 possibilities:
4P
: For units with 2 batteries (4 pipes).
Change-Over
: For devices with a single battery but which must operate either in Cold or Heat with
automatic inversion.
CO
: For devices with only one battery and operating in Cold mode only.
HO
: For devices with only one battery and operating in Heat mode only.
MENU
Time slot
Time/Date
Alarm
Fan
Configuration
Language
SELECT CONFIGURATION
4P
Change-over
CO
HO
This configuration is only carried out via Modbus.
For permanent ventilation, it is enough to enter the minimum value in register 111, as shown in the table.
For cyclic ventilation, the number 32,768 must be removed from the minimum value in the table.
Example: for a minimum value of 30%, you must enter +30 - 32 768 in register 111, i.e. -32 738.
Ventilation can operate in 2 modes:
²
permanent ventilation, ventilation operates at minimum speed even when the set temperature is
reached
²
cyclic ventilation, ventilation stops as soon as the temperature reaches the setpoint.
Information
As standard, the
TControl POD glass EC
is configured for cyclic ventilation. Configuration via the
display is only done by setting the minimum speed value. The
TControl POD glass EC
automatically
integrates the correction.
Setting
4P
Change-Over
CO
HO
Input 1
Not used
Change-Over sensor
(NTC 10k)
Change-Over contact
NC
Change-Over contact
NO
Input 2 (230 V)
In-use contact NO
In-use contact NO
In-use contact NO
In-use contact NO
Ventilation selection
No
No
No
No
Post-ventilation (s)
30
30
30
30
100% ventilation hysteresis
4
4
4
4
Number of ventilation stages
3
3
3
3
7.6.1. PRE-CONFIGURATION