English
26 TControl POD glass EC
Modbus Input Register (R)
Address-I Min. Max. Gain Name
Description
511
0
50
0.1 Heat setpoint
0-500
≙
0-50.0°C
Example: 21.5°C = 215
512
0
50
0.1 Cold setpoint
0-500
≙
0-50.0°C
Example: 21.5°C = 215
513
0
15
0.1 Setpoint offset
0-150
≙
0-15.0°C
Example: 3.0°C = 30
514
0
50
0.1 Internal sensor temperature
0-500
≙
0-50.0°C
Example: 21.5°C = 215
515
0
50
0.1 External sensor temperature
0-500
≙
0-50.0°C
Example: 21.5°C = 215
516
0
1
-
Heat output
0: Open
1: Closed
517
0
1
-
Cold output
0: Open
1: Closed
518
0
10
0.1 Ventilation status
0-100 = 0-10 V Manual
-256..-156 (=0xFF00-0xFF64): Automatic with value in
volts
519
0
1
-
Input status 1
0: Open
1: Closed
520
0
1
-
Input status 2
0: Open
1: Closed
521
-1
1
-
In-use status
0: Not in-use
1: In-use
-1: 0xFFFF: Input inactive
522
-1
1
-
Dew point status
0: inactive
1: active
-1: 0xFFFF: Input inactive
523
-1
1
-
Window contact status
0: Window closed
1: Open window
-1 = 0xFFFF: Input inactive
525
0
2
-
Control mode
0: Off
1: Heat
2: Cool
526
0
1
-
Temperature alarm status
0: No alarm
1: Alarm detected