background image

Table of Contents

General Information .................................................5

1.1 

List of Information .........................................................5

1.2 

Notes on the Documentation .......................................5

1.3 

Using the Systemair-Cloud ...........................................6

1.4 

Heat Pump Special Rate/Utility Lock ..........................6

1.5 

Notes on Planning and Installation .............................6

Important Safety Information ..................................7

2.1 

Safety Notes ...................................................................7

2.2 Personnel ........................................................................8
2.3 

Intended Use ..................................................................8

2.4 

Handing over to the Customer ................................. 9

2.5 CE-Marking .....................................................................9
2.6 Warranty .........................................................................9

Delivery and Accessories .......................................10

3.1 

Delivery Contents ....................................................... 10

3.2 

Accessories (not included in the delivery) .............. 10

Description of the System ......................................12

4.1 

The Combi Unit Genius in Detail ............................... 12

4.2 

Operation in Combination with Room Air 

 

Independent Fireplaces (Furnace Function) ............ 13

4.3 

Technical Data ............................................................. 14

4.4 

Name Plate .................................................................. 16

Transport and Storage ............................................17

6 Assembly ................................................................17

6.1 

Safety Information ...................................................... 17

6.2 

Location Dimensions  ................................................. 18

6.3 Preparation .............................................................18
6.4 Location ..................................................................19
6.5 Connections ............................................................20

6.6 Electrical 

Connection ..............................................23

6.7 

Connection Air Duct System ...................................24

7 Commissioning .......................................................25

7.1 

First Commissioning ................................................... 25

7.2 

Fill and Vent ................................................................. 25

7.3 

Internet Connection  ................................................... 27

Maintenance / Remedying Faults .........................31

8.1 

Alarm Status ................................................................ 31

8.2 

Ventilation Module ..................................................... 37

8.3 

Heat Pump Module ..................................................... 39

8.4 

Hot Water Module ...................................................... 40

9 Service ....................................................................42

9.1 

Ventilation Module ..................................................... 42

9.2 

Heat Pump Module / Components ........................... 43

9.3 Control .......................................................................... 46

10 

Operation/Control via Internet/App ......................47

10.1  General Information ................................................... 47

10.2  Access - Log on .......................................................48

10.3  Service Level Settings ................................................ 48
10.4  Actual Value / Setpoint .............................................. 50
10.5  Alarm Status ................................................................ 55
10.6 Input/Output ............................................................... 56
10.7  Time Program .............................................................. 59
10.8 Settings ........................................................................ 62
10.9 Manual/Auto ............................................................... 80
10.10  Chart Function ............................................................. 81

11 

Control via Display ..................................................87

11.1 Display .......................................................................... 87
11.2 Access .......................................................................... 87
11.3  Alarm Log .................................................................... 88
11.4  Read Alarm .................................................................. 88
11.5  Display Tree Logic ....................................................... 89

12 

Room Controller ......................................................99

12.1 Description/Operation ................................................ 99

13 

Comfort and Energy Efficiency

............................ 100

13.1  Utility Company Rates ..............................................100
13.2  Setpoint Temperatures/Settings .............................100
13.3  Fan Stages .................................................................103

14 

Declaration of Conformity ................................... 104

15 Glossary ............................................................... 105
16 Appendix ............................................................. 106

3

Genius - V 1.0

 

Содержание Combi Unit Genius

Страница 1: ...stallation Operation and Maintenance Instructions for qualified installers Combi Unit Genius Controlled Residential Ventilation with Heat Recovery Heating Hot Water Generation Cooling EN page 1 page 1...

Страница 2: ...not be derived from our information The information does not release the user from his own assess ments and examinations It must be noted that our products are subject to a natural wear and ageing pr...

Страница 3: ...ctrical Connection 23 6 7 Connection Air Duct System 24 7 Commissioning 25 7 1 First Commissioning 25 7 2 Fill and Vent 25 7 3 Internet Connection 27 8 Maintenance Remedying Faults 31 8 1 Alarm Status...

Страница 4: ...4 Genius V 1 0...

Страница 5: ...OTE Useful information and instructions 1 1 1 Safety Symbols General symbol for danger Risk of burns Electrical voltage 1 1 2 Presentation of Handling Instructions Handling instruction Handling instru...

Страница 6: ...nd electrical installation Increased air volume flow during heating or cooling operation This results in a larger supply air duct system High air velocities and noise development can be avoided Air ti...

Страница 7: ...rofit it if required Do not use the ventilation system while the floor screed is drying because damage to the ventilation unit may occur due to the formation of excessive condensation Any operation du...

Страница 8: ...180 m living area Standard Energy Efficient House according to EnEV 2016 formerly Energy Efficient House 70 max 140 m living area Furthermore the building needs to be appropriately airtight Recommende...

Страница 9: ...2006 42 EC see EC Declaration of Conformity in the appendix 2 6 Warranty The warranty for the combi unit Genius determines itself after the contractual definitions our offers as well as in supplement...

Страница 10: ...the drinking water tank the electrical cabinet and the hydraulic connections 2 The heat pump module The heat pump module includes the complete pre installed cooling circuit The cooling circuit also co...

Страница 11: ...s Air to air geothermal heat exchanger The air to air geothermal heat exchanger should be connected to the outdoor air of the heat pump to ensure higher energy efficiency A combined connection to the...

Страница 12: ...air to air and air to water heat pump for heating cooling and hot water Steplessly controlled compressor to modulate the power exactly to the need of heating and cooling energy Hot water module 150 li...

Страница 13: ...formation of a negative pressure This can be realized either through mutual operation ventilation system switches off when operating the fireplace or by a pressure controlled mode ventilation system s...

Страница 14: ...170 version L Max power input secondary air fan W 170 Max input power compressor W 1800 max power input fans module ventilation W each 80 max power input fan module heat pump W 170 Power input storag...

Страница 15: ...60 Outdoor air heating pump DN 250 Extract air DN 160 Supply air DN 200 Secondary air DN 200 Exhaust air ventilation heat pump DN 250 Other Refrigerant R410A Filling quantity refrigerant kg 1 4 Storag...

Страница 16: ...gerant refrigerant volume Systemair GmbH D 97944 Windischbuch Germany Seeh fer Str 45 Tel 49 7930 9272 0 eMail info systemair de www systemair de Fax 49 7930 9272 92 0 date heating capacity max weight...

Страница 17: ...nt Position the unit only on a level ground WARNING Damage to the hydraulic connections The hydraulic connections can tear Do not transport the combi unit by the hydraulic connections Transportation n...

Страница 18: ...sound insulation mats Install the unit in a frost free room on a load bearing floor The floor must be horizontal level solid and durable Place the unit only on a floating screed when this is done prop...

Страница 19: ...panel of the basic module access to the plug Hold the side panel and remove it Disconnect the 3 plug connectors in the upper part Remove the module Lead the plugs through the cover opening Pull out th...

Страница 20: ...be removed WARNING Risk of impact or crushing due to falling parts The panels are not fixed They can fall down after loosening the screws Hold the panels during loosening and put it down to the floor...

Страница 21: ...valving pressure 6 bar 13 Drain valve Figure 6 Rear side connections with cold water safety group Field installation connections see Fig Figure 6 Required field installation Cold water safety group w...

Страница 22: ...re 7 or Ensure a minimum connection distance of 2 5 m TIP Install a pre filter into the outdoor air intake of the heat pump see Figure 7 pos 1 to protect the fan and the heat exchanger 6 5 4 Condensat...

Страница 23: ...ircuit breaker 30 mA Remove the left side and the front panel to access to the electrical cabinet Remove the cover of the electrical cabinet Lead the electrical connections and the control cables thro...

Страница 24: ...livered display is ready to plug The display can be fixed by the enclosed magnet e g to the rear side The display also can be wall mounted preferable the installation room 6 6 5 PTC Elements The PTC e...

Страница 25: ...uced 7 2 Fill and Vent 7 2 1 Remove Panels WARNING Risk of impact or crushing due to falling parts The panels are not fixed They can fall down after loosening the screws Hold the panels during looseni...

Страница 26: ...valve of the heat pump module 1 Connect the fill and drain valve 3 with a hose to the water network Open the fill and drain valve and flush the hydraulic circuit bubble free 7 2 4 Fill the Tank for th...

Страница 27: ...the building service centre to activate the room controller First visit the website to define the room addresses in Settings activate supply air rooms Log on to the website Define the room addresses...

Страница 28: ...ered data with the room sensors NOTE The same settings can be carried out via display 7 3 3 2 Settings and Adjustment of the Air Volume Flows The regulation of the volume flows must be done by a speci...

Страница 29: ...er the adjustment Fan speed settings with Settings speed percentage Speed Supply air fan Speed at intense ventilation 65 Speed at nominal ventilation 50 Speed at reduced ventilation 35 Speed at hum pr...

Страница 30: ...y with it the maximum heating cooling power not the power for hot water production must be limited according to the specifications of the planer the configuration by Systemair Secondary air fan Parall...

Страница 31: ...ry air fan Alarm class B normal All status Manual operation supply air fan Alarm class C normal normal Manual operation extract air fan Alarm class C normal Blocked Manual operation secondary air fan...

Страница 32: ...es to display can be selected with this field Class A Class B Class C Incidents Display status All status The alarm status to display can be selected with this field normal Blocked Confirmed Cancelled...

Страница 33: ...ymbol Confirmed to confirm the alarm Block Click the symbol Blocked to block the alarm Only possible in the service level Released Click the symbol Released to release the alarm Only possible in the s...

Страница 34: ...ng In addition sum alarm will also be activated mostly for heat pump errors The exact description of the alarm is shown in the list If it is a C alarm which automatically resets itself the heat pump s...

Страница 35: ...rooms Controlled residential ventilation is out of service Heating and cooling operation remains active with decreased performance Hot water generation remains fully functional Remedying faults Fix t...

Страница 36: ...s functional Remedying faults Fix the alarm or let it be fixed by a service technician Select the alarm Click the symbol Confirm Manual operation C Alarm The fans can be controlled manually but only f...

Страница 37: ...the filter a if the filter life is reached b if the behaviour of the combi unit indicates a contaminated filter The filter life depends on the air pollution at the installation place but it must not e...

Страница 38: ...nge 8 2 1 2 Check and Clean Rotating Heat Exchanger 1 Legend 1 Heat exchanger unit Figure 13 Check and clean rotating heat exchanger 9 9 Precondition The combi unit is disconnected from the power supp...

Страница 39: ...aporator on the right intake in dry state preferably with compressed air caution against possible contami nation in the room Check and maintenance of the condensate drain Check and maintenance interva...

Страница 40: ...y pressure 1 bar Remove the protection cap from the filling valve Depressurise the water bearing side by the fill and drain valve Check the pressure of the expansion tank with a pressure gauge Fill th...

Страница 41: ...ess to the storage tank Lift the black tank cover Remove the black tank cover and the sealing Access to the anode connection 1 Disconnect the potential equalisation cable from the tank Connect an ampe...

Страница 42: ...Caution The alarm remains active 9 1 1 2 Unit Characteristics in Summer The heat pump is only working for hot water generation Return to normal operation 9 1 1 3 Clear Rotor Alarm Block the alarm Ope...

Страница 43: ...fer medium The heat pump is ready for operation so that no work must be carried out on the refrigeration circuit The controller automatically takes over the activation of the heat pump as well as the...

Страница 44: ...9 2 3 Temperature Sensors NTC sensors are used to measure the operating temperatures such as suction and hot gas in the refrigeration circuit These are designed as contact sensor for the ducts T C R k...

Страница 45: ...ater Close the cold water supply Connect a hose to the drain valve Open a water tapping point during the drain procedure to prevent negative pressure Drain the water of the tank by one third about 50...

Страница 46: ...centre Genius can preferably be adjusted by a notebook PC or by the Systemair App Android phone This pro vides a perfect overview of all user functions and parameters self explanatory The control of...

Страница 47: ...etters The formatting of the settings is done by the program Examples Enter 2 8 as starting point for holiday 2 the program converts to 2 Aug Or enter 47 as setpoint the program converts to 47 C 10 1...

Страница 48: ...Here you see the most important setpoint and actual values of your combi unit Actual value Setpoint Here you can see important values black values or set values blue values Alarm status You can see an...

Страница 49: ...tatus 1 Active Actual value temperature 21 5 C Setpoint value temperature 21 0 C Room 2 Bedroom Status 1 Active Actual value temperature 20 9 C Setpoint value temperature 21 0 C Unit Status Rotor oper...

Страница 50: ...21 5 C Room 3 Lea Furnace operation Off Status Active Manual cooling No PTC element blocked Manual time 60 min Actual value temperature 21 3 C Heating Fixed setp Setpoint value temperature 21 0 C Cool...

Страница 51: ...egionella mode see Hot water HP Defrost The heat pump HP in reverse operation the heat pump heat exchanger will be defrosted Normal operation is temporarily interrupted The PTC elements are driven wit...

Страница 52: ...tically after one hour Off Switching off must be ensured for safety reasons It can be used for manual ventila tion e g summer 10 4 1 3 Setpoint Temperature Display Shows the actual room temperature af...

Страница 53: ...ration Settings Yes No Default setting No Legionella mode If the legionella mode is activated the drinking water is once heated to 60 C in the night of Sunday to Monday once a week Settings Yes No Def...

Страница 54: ...rnace Function Operation in Combination with Room Air Independent Fireplaces In this constellation the heating fan can be manually controlled even without heating demand of the heat pump WARNING Poiso...

Страница 55: ...an active or normal element The PTC displays only appear in the heating mode Display Illumination After a certain period the room controller will switch to standby mode The intensity of the display i...

Страница 56: ...gue outputs Requested capacity comp 0 AA1 supply air fan control 6 0 V Actual capacity comp 0 AA2 extract air fan control 5 5 V Actual speed comp 0 U s AA3 secondary air fan control 0 0 V Status envel...

Страница 57: ...DE2 Pressure monitoring alarm Off DE3 PV Off DE4 Rotor operation Off DE1 EVU Set to Off as long as the forced shutdown of the utility company is active see Ser vice manual Wiring Diagram DE2 Pressure...

Страница 58: ...torage charge pump Off DA7 Heating rod HW Off DA1 Relay heat pump operation see Settings DA2 Change over After the switch off point has been reached see Settings the signal switches It can be used as...

Страница 59: ...00 00 00 Holiday 13 1 Jan 1 Jan Sunday 00 00 24 00 00 00 00 00 Holiday 14 1 Jan 1 Jan Holiday 00 00 24 00 00 00 00 00 Holiday 15 1 Jan 1 Jan Heating Cooling Ventilation Start Stop Start Stop Holiday...

Страница 60: ...within the time slots in normal operation Outside these time slots the unit is in setback operation NOTE When using a circulation pump it must be externally controlled see 13 2 3 Hot Water Generation...

Страница 61: ...e residential unit Heating Average room temperature 18 C adjustable frost protection avoids cooling down of the residential unit see Settings Cooling Cooling is switched off for energy saving Hot wate...

Страница 62: ...237 Actual value 21 7 C Room 6 Setpoint 21 8 C Modbus room address ELA 200 Control output 43 C Default settings rooms P band 3 C Room 1 I time 20 s Room sensor internal Sup air temp con Setpoint room...

Страница 63: ...mp if HW temp S 1 C Room sensor internal Stop charge pump if HW temp S 2 C Setpoint room temperature 20 0 C Extended running pump 150 s Temperature rise 3 C Default value time program Automatic Temper...

Страница 64: ...rotor alarm 19 C Control parameters Room controller Actual value 21 7 C Setpoint 21 8 C Control output 43 C P band 3 C I time 20 s Sup air temp con Actual value 32 3 C Setpoint 42 6 C Control output...

Страница 65: ...ithin this neutral zone 20 26 C the unit remains in Heating mode with the cor responding setpoint values Adjustment range Heating 10 23 C cooling 23 34 C Factory settings outdoor temperature 18 C and...

Страница 66: ...n the Actual Value Setpoint page An offset is possible there Example The average room temperature setpoint changes from 25 C to 24 C with an outdoor temperature of 30 C and an offset of 1 C The curve...

Страница 67: ...vel by means of PTCs This means that every room can be controlled individually The PTC start delay is out of function When selecting the individual room temperature control the PTC function must be ac...

Страница 68: ...C 3 C Default setting 0 C Heating Setback temperature Setback temperature This parameter defines the room temperature setpoint decrease during offset in heating mode see 10 7 2 Time Program page 60 Ex...

Страница 69: ...alarm 19 C NOTE Blocking of alarms can cause uncontrollable malfunctions Use this function only in exceptional cases and after consulting specialised personnel Control parameters Control parameters Ro...

Страница 70: ...dershot during heat pump standstill in winter the PTC elements will be activated to min power to avoid draughts PTC function On In this case a setpoint decrease can be recommended Heating Min Supply a...

Страница 71: ...he lower the values can be set Manual operation default setting 40 C may be appropriate depending on user behaviour Offset the temperature curve Offset Adjustment range 5 C 5 C Default setting 0 C Hea...

Страница 72: ...Commissioning and 10 8 1 3 Night cooling The speed values are generally set once during commissioning within this menu Secondary air fan Delivery setting Adjustment range Parallel offset speed 100 70...

Страница 73: ...he fan speed is automatically changed in order to protect the rotary heat transfer This is only done at very low outdoor temperatures and for a certain period of time Within the defrost function five...

Страница 74: ...of 44 C and end the generation at 47 C Extended running pump The pump continues running for 150 seconds so that the heat pump can release all the heat Hot Water Default value time program Automatic A...

Страница 75: ...eater starts P Gain preheater Default setting 2 The preheater can be steplessly adjusted from 0 100 Using this value it is possible to set the speed at which the power increases NOTE A preheater is re...

Страница 76: ...y low temperature reduction It can not replace active heat pump cooling 10 8 1 4 Filter alarm Filter alarm Reset filter life No Number of months for filter change 12 Number of months since last filter...

Страница 77: ...rvice centre Genius is designed for a maximum of 10 rooms Since heating cooling takes place in the supply air rooms in general controllers are only installed in these rooms Exception if extract air ro...

Страница 78: ...C I time 20 s Room designation Living room Room 2 Room sensor internal Window contact No NO NC NO Setpoint room sensor 20 0 C Temperature rise 3 C Temperature setback 3 C P band 3 C I time 20 s Room d...

Страница 79: ...PID controllers are preset and need normally no adjustment If changes must be made this must be carried out only by qualified personnel Room designation Room designation Living room Any room zone can...

Страница 80: ...DO6 Status Auto Pump Off Heating rod HW DO7 Status Auto Heating rod HW Off Preheater AO4 Status Auto Control output 0 0 V This page is exclusively available in the service level It is used for manual...

Страница 81: ...al Scale Last value Display Actual temperature left 25 0 C Actual temperature left 24 1 C Actual temperature left 24 7 C Actual temperature left 45 5 C Der Status is defined by the following digit seq...

Страница 82: ...highlighted scale up with the up button Move the highlighted scale down with the down button TIP It may be useful to record the status of the unit rotor operation defrost etc illustrated with figures...

Страница 83: ...Room Temperature Right 21 0 C Output power Right 100 Compressor Actual Capacity Right 0 1 3 2 4 5 6 Figure 30 Values to the display example 1 Display of the graphs and values 2 Signal Name of the sign...

Страница 84: ...ancel You will see the change immediately in the chart being dis played Figure 31 Properties 10 10 2 Command Remove all signals Remove all signals Remove all signals Click the symbol Confirm the secur...

Страница 85: ...ple marks Click the symbol Figure 34 Sample marks hidden 10 10 5 Command Hide show ruler Show ruler Hide show ruler Click the symbol The ruler and the corresponding values will be displayed Value at r...

Страница 86: ...n the Copy window in the Pull down menu Cancel Click Cancel to cancel the action Copy values to clipboard Click OK to add the settings Click OK in the Confirmation window The values have been copied t...

Страница 87: ...confirm 8 LEFT button 9 ALARM button LEDs Alarm LED red The alarm LED is illuminated when the combi unit has triggered an alarm Input Enable LED yellow In some menus there are parameters that can be...

Страница 88: ...values with the up or down buttons Push OK button The new value is now confirmed 11 3 Alarm Log NOTE The alarm log of the unit can only be read by the display Therefore it is especially important in...

Страница 89: ...mber 11291470 Operation mode Heat pump mode Heating and Cooling Actual HP status Heating Temp setpoint Heat pump Off Mode Heating power 0 Ventilation mode Day normal Night normal Furnace operation Off...

Страница 90: ...ng 0 Room 2 Room 2 Room temp 21 C Desired temp 21 C PTC heating 0 Alarm event Hot Water Hot Water HW temp 46 C Desired temp HW 45 C HW temp holidays 30 C PTC Fast charge HW No Activate legionella func...

Страница 91: ...0 for 2 00 00 00 00 Week program HW Running time Tuesday for 1 00 00 24 00 for 2 00 00 00 00 etc Running time Holidays for 1 00 00 24 00 for 2 00 00 00 00 Week program HW Running time Monday for 1 00...

Страница 92: ...s Heat pump Hot Water Cooling Mode setp Cooling Mode setp Type of Setpoint Outdoor temp Managed Setpoint cooling curve 32 26 C 28 24 C 30 25 C 26 23 C Shift 0 C Heating Mode setp Type of Setpoint Outd...

Страница 93: ...22 C Filter change Reset alarm time Filter alarm Reset alarm No Set alarm time Filter life activation 12 mon Time since last change 0 mon Service settings Access Rights Heat pump Heat pump Modbus addr...

Страница 94: ...Modbus address 197 Language Room 2 Modbus address 39 etc After activation of the rooms Config Room 1 Room 1 Setpoint temp 20 0 C Deviation 3 C Deviation 3 C Room 1 P band 3 C I band 3 C Room 1 Sensor...

Страница 95: ...lay settings lines will be shown only after log on Operation mode Manual Auto Manual Auto PTC room 1 to 10 Auto Manual setpoint 0 0 V Manual Auto Supply air fan Auto Manual setpoint 0 0 V Manual Auto...

Страница 96: ...t hysteresis 0 3 C Stop hysteresis 0 3 C Start delay 60sec Stop delay 120sec Service settings Speed Supply air fan SAF intense 70 SAF normal 50 SAF reduced 35 SAF humidity protect 15 SAF night cool 85...

Страница 97: ...Water mode Automatic Start pump if Temp Setpoint 1 C Stop charge pump Temp Setpoint 2 C Extended running HW pump 150 s 1 1 Do not to change this value Service settings PTC PTC function On PTC start d...

Страница 98: ...us Auto Man Output 0 0 V AO 2 Speed ETA Output 5 0 V Status Auto Man Output 0 0 V AO 3 Speed SEC Output 5 0 V Status Auto Man Output 0 0 V AO 4 Preheater Output 0 0 V Status Auto Man Output 0 0 V Digi...

Страница 99: ...nt temperatures NOTE These changes can be done via internet App and are described there Figure 39 Room controller 1 2 3 4 5 6 10 9 7 8 1 Occupation Room active 2 Actual room temperature C 3 Service re...

Страница 100: ...ump tariff is available without forced interruption 13 2 Setpoint Temperatures Settings 13 2 1 Winter Operation If the operating limits and the requirements meet planning and installation the system w...

Страница 101: ...the outdoor compensated room setpoint offset factory setting because an auto matic setpoint increase can be avoided or compensated 13 2 2 Summer Operation Active cooling Due to modern building standa...

Страница 102: ...absence the setpoint temperature must be raised or the legionella function must be activated Electric heating rod The combi unit Genius includes an electric heating rod of 3 kW It ensures hot water c...

Страница 103: ...flow rate is adjusted by the specialist company during commissioning Ventilation system settings Ventilation for humidity protection Use this function only in case of longer absence NOTE Larger humid...

Страница 104: ...ty of household and similar electrical appliances Part 1 General requirements DIN EN 13141 10 2008 Ventilation for buildings Performance testing of components products for residential ventilation Part...

Страница 105: ...your absence or sleep Rotating heat exchanger Due to the rotation of the heat exchanger supply and extract air flow through in one revolution alternately by the cells Thus transfers the heat regenera...

Страница 106: ......

Страница 107: ......

Страница 108: ......

Страница 109: ......

Страница 110: ......

Страница 111: ......

Страница 112: ......

Страница 113: ......

Страница 114: ......

Страница 115: ......

Страница 116: ......

Страница 117: ......

Страница 118: ......

Страница 119: ......

Страница 120: ......

Страница 121: ......

Страница 122: ...Terminal block ventilation module 122 Appendix Genius V 1 0...

Страница 123: ......

Страница 124: ...Systemair GmbH Seeh fer Str 45 D 97944 Windischbuch Tel 49 0 7930 9272 0 Fax 49 0 7930 9273 92 info systemair de www systemair de Article no date a...

Отзывы: