10.6.2 Analogue Inputs
The analogue inputs show the temperatures of the various sensors as well as the operating signal / mutual fan monitoring.
Analogue inputs
Temperature
AE1
Outdoor temperature
7.1 °C
AE2
Supply air temperature
23.4 °C
AE4
Extract air temperature
22.0 °C
UAE1
Hot water temperature
44.6 °C
UAE2
Supply air fan monitoring
10 V
UAE3
Extract air fan monitoring
10 V
UAE4
Secondary air fan monitoring
10 V
UA 2 ... 4
Relevant for the fan monitoring (see "8.1.4 Confirm Faults / Procedure" page 57).
10 V: failure-free operation
0 V: triggers an alarm
10.6.3 Digital Inputs
Digital inputs show operating signals.
Digital inputs
DE1
EVU status
On
DE2
Pressure monitoring alarm
Off
DE3
PV
Off
DE4
Rotor operation
Off
DE1 EVU
Set to
Off
, as long as the forced shutdown of the utility company is active. see “Ser-
vice manual/Wiring Diagram”.
DE2 Pressure monitoring
If there is a fireplace and pressure monitoring (provided on-site by the client) is
required, it is connected here. see “Service manual/Wiring Diagram”.
WARNING
Scalding
Risk of scalds with water temperatures higher than 43 °C.
» The client must provide protection against scalding!
DE3 PV
If this input receives a signal from an inverter of a photovoltaic system, the hot water
will be heated to a temperature of 60°C using an electric heating rod.
DE4, rotor operation On/Off
Changes during rotor operation steadily from
Off
to
On
. This is not an error, but is
caused by the rotor monitoring.
57
Genius - V 1.0
Operation/Control via Internet/App
Содержание Combi Unit Genius
Страница 4: ...4 Genius V 1 0...
Страница 106: ......
Страница 107: ......
Страница 108: ......
Страница 109: ......
Страница 110: ......
Страница 111: ......
Страница 112: ......
Страница 113: ......
Страница 114: ......
Страница 115: ......
Страница 116: ......
Страница 117: ......
Страница 118: ......
Страница 119: ......
Страница 120: ......
Страница 121: ......
Страница 122: ...Terminal block ventilation module 122 Appendix Genius V 1 0...
Страница 123: ......