Activated night cooling
Night cooling activated
When night cooling is enabled, the speeds will automatically be increased during a
fixed period of time (see Service, Settings). Thus, the air flow and the cooling capac
-
ity increases.
The following factors are preset for the
Activated night cooling
:
•
The function is active when the average outdoor temperature was higher than 22
°C from 12:00 to 17:00.
•
The function is active from 24:00 to 6:00.
•
The function remains active at night with outdoor temperatures between 5 °C and
18 °C. Below or above it is interrupted.
•
The function is terminated when the average room temperature in the house falls
below 20 °C.
These factory settings can be adjusted on demand, the fan request below the
Speed
.
Setting:
no settings required
Default setting:
85 %, speed level for
supply and extract air fan
NOTE
A passive cooling by the rotary heat exchanger can only provide a relatively low temperature reduction. It can not
replace active heat pump cooling.
10.8.1.4 Filter alarm
Filter alarm
Reset filter life
No
Number of months for filter change
12
Number of months since last filter change
1
At the end of the set months for filter change, an alarm message appears (see
Alarm status
). Once the filter has been changed, the func
-
tion must be reset. The alarm remains visible even when it has been confirmed.
Reset filter alarm
The alarm remains active until the filter life is reset. No confirm response.
"
Change the filter (see Filter Change).
"
Set
Reset filter life
to Yes.
"
Acknowledge filter alarm at
Alarm status
.
»
The filter alarm is now reset. Number of months since last filter change is set to zero.
Filter alarm
Reset filter life
Yes
Ú
Number of months for filter change
No
Number of months since last filter change
Yes
NOTE
Shows the number of months for filter changes:
a) down, if the filter is heavily contaminated.
b) up, if the filter still has a very good quality, max. 12 months.
10.8.1.5 E-mail
Alarms via e-mail
No
e-mail address
76
Operation/Control via Internet/App
Genius - V 1.0
Содержание Combi Unit Genius
Страница 4: ...4 Genius V 1 0...
Страница 106: ......
Страница 107: ......
Страница 108: ......
Страница 109: ......
Страница 110: ......
Страница 111: ......
Страница 112: ......
Страница 113: ......
Страница 114: ......
Страница 115: ......
Страница 116: ......
Страница 117: ......
Страница 118: ......
Страница 119: ......
Страница 120: ......
Страница 121: ......
Страница 122: ...Terminal block ventilation module 122 Appendix Genius V 1 0...
Страница 123: ......