FAAST 7100X
INSTALLATION AND MAINTENANCE INSTRUCTIONS
© Pertronic Industries Ltd
19
FAAST XS (7100X) Installation Guide Iss 1.0, 201606
(vi) the amended Sensitivity settings will be reflected in the Sensor settings in Configuration – refer to
Threshold Levels (%/m)
under
Alarm Threshold and Delay
in
Configuration \ Sensor
- in the screenshot below, the
Day Threshold Levels
reflect the fact the
Day
Sensitivity has been
amended, while
Night
and
Weekend
are default values
-
Night
and
Weekend
Threshold Levels can be sequentially updated to match the
Day
values
simply by pressing the arrow or alternately Night and Weekend settings can be customised
(vii) Select the device from the tree, right click and select
Device Information.
- record the following details in Section H : FAAST
XS System Validation
Form:
a. Fan Speed RPM
b. Flow Velocity Chamber
c. Flow Velocity Inlet
d. Flow Base Chamber
e. Flow Base Inlet
- Flow Velocity values represent the current flow
rate through the Chamber and Inlet
- Flow Base values represent the flow rates as
measured during the BaseLining process
Flows are measured in m/s, while PipeIQ
calculates flow rates in l/min - a Flow Rate
Conversion Table is available at Section G