(iii) identify cells which do not meet the system constraints – highlighted in
red
(iv) select
Settings \ Constraints
, then
CUSTOM
- first review the
Sensitivity
settings used by
VEWFD
,
EWFD
or
SFD
to identify appropriate settings
for the system being configured, then apply settings suitable to the
CUSTOM
constraints
(v) acknowledge any advisory notices, then verify all Settings meet the Constraints
- verify
Flow Balance
: should be
≥
0.70
- select Auto Balance to maximise
Flow Balance
and manually adjust
Hole Diameters
if required
to achieve
Flow Balance
≥
0.70