SECTION C : CONFIGURING FAAST XS (7000 SERIES) IN PIPEIQ
A. Configuration:
T
he following screen shots identify the parameters which are configurable on the 7000 Series FAAST XS
devices. Review all parameters to ensure they are appropriate, taking particular care to ensure the
coloured
parameters are correct
a) General:
(i) Model
Number:
select 7100X
(ii) General:
complete the details for identifying
the Name and Location of the detector and
the Contact Person
(iii) Device Details:
-
Serial Number:
this will self-complete after
connection to the detector
-
Enable DayLight Saving:
if required,
select Custom, then:
Starts On: Last Sunday September 02:00
Ends On: 1st Sunday April 03:00
Time Saved: 60 min
-
Date and Time:
should ONLY be updated when connected to the FAAST detector.
Either complete the actual time at Device or if the PC time is correct, simply select the arrow to
download the PC time to the detector
-
Time Format:
select either 12 Hour or 24 Hour format
-
Trend Log:
select the Frequency for logging the detector functions to the Trend Log – note that as the
frequency increases, the duration of the Log reduces (Capacity/Frequency=Duration of Log)
- the rate is limited to a range of 1 to 60 minute or 1 to
24 hour periods
- depending on the rate chosen, data can be collected for 72
hours up to 11.8 years
b) Sensor:
(i) Alarm Thresholds and Delay:
Enable
or
Disable
Acclimate Mode:
Acclimate Mode:
-
Enable :
enter the
Min
and
Max
Sensitivity Level for each activation level
-
Disable :
enables
Threshold Mode
Threshold Levels (%/m):
- enter the required
Day
,
Night
and
Weekend
Sensitivity Level for each
activation level
Note: the Threshold Levels may
alternatively be set during Design – refer to
Design
Delay (sec):
introduces a specified delay
and verifies if the Alarm condition still exists
before triggering the Alarm
(ii) Night
Mode:
select
Start Time
and
End Time
(iii) Alarm/Fault Relay Latching:
Minor (Fault),
Alert, Fire 1 and Fire 2 can be individually configured to be Latching
or Non-Latching
7100X Only