Parameter setting
Page 50/55
SYCLOPE TERE’O Touch XL
®
Installation, starting, and programming instructions
Mesure
Commande de régulation
Consigne de régulation
Hystérésis
100%
0%
Hysteresis
Dosing action
Regulation setpoint
Measure
When the dosing direction of the pH channel is configured in upstream mode.
In proportional mode, when the error (setpoint - measurement) is equal to the proportional
band, the control requirement is 100%, by reducing the value of the proportional band, you
increase the dosing control for the same measurement value.
In hysteresis mode, as soon as the error (setpoint - measurement) is greater than the
hysteresis value, the regulation requirement is 100%.
3)
Dosing
Pressing the « Dosing » button opens the programming window.
Change dosing direction:
Here you can choose the dosing direction depending on
the type of treatment and the type of product injected.
Maximum dosing time:
This button is used to enter a maximum operating time of
the pump over a period of 24 hours. This max time is
configurable between 0 and 1440 minutes.
If the time of use of the pump exceeds this duration, in a
period of 24 hours the dosing stops and it will resume only after
the intervention of the user who will have to cancel this alarm.
At the end of 24 hours without exceeding the time, the
latter is reset automatically
By setting 0 as the maximum dosing time, the time counting function is deactivated.
Settings
pH channel
Dosing
Control direction selection
Down
Up
120
Maximum dosing time
in minutes
Mesure
Commande de régulation
Consigne de régulation
Bande proportionnelle
100%
0%
Regulation setpoint
Measure
Proportional band
Dosing action