GB.COMPACTAHSK.210520
Registered design. The company reserves the right to make design changes without prior notice.
58 www.swegon.com
Function
Factory-preset value
Adjusted value
"Heating BOOST"
Function, Off/On
X Inact.
Active
Inact.
Active
Start limit, SA temp. (°C)
3,0
Ramp time (%)
2.5
Exercizing
Cooling relay 1
X Inact.
Pump
P+V
Valve
Inact.
Pump
P+V
Valve
Cooling relay 2
X Inact.
Pump
P+V
Valve
Inact.
Pump
P+V
Valve
Exercise period
3 Min.
Interval
24 hrs.
Control reaction speed
Step duration (s)
300
Outdoor temp. limit
Step 1 (°C)
3,0
Step 2 (°C)
5,0
Step 3 (°C)
7,0
Reset time (s)
480
Cool. min. SA flow (m³s)
008
Cool. min. EA flow (m³s)
0,08
Neutral zone (°C)
2,0
"Cooling BOOST"
X Inact.
Comf.
Econ.
Sequ.
Inact.
Comf.
Econ.
Sequ.
Comf.+econ.
Econ.+sequ.
Comf.+econ.
Econ.+sequ.
Start limit SA temp. (°C)
3,0
Ramp time
(%)
2.5
Inputs/Outputs
Relay 1
A Alarm output 4)
Relay 2
B Alarm output 4)
Input 1
External low speed 5)
Input 2
External high speed 5)
"IQnomic Plus"
I/O Module No. 0
Input/Output
connections
X Inact.
Active
Inact.
Active
I/O Module No. 3
Ext. monitoring
X Inact.
Active
Inact.
Active
I/O Module No. 6
Cooling
X Inact.
Active
Inact.
Active
I/O Module No. 7
AYC
X Inact.
Active
Inact.
Active
Alarm setting
Fire alarm function
Internal fire alarms
X Inact.
Active
Inact.
Active
External fire alarm
Alarm resetting
X Man.
Auto
Man.
Auto
Fan op. in the event of a fire
X Inact.
SA
EA
SA+EA
Inact.
SA
EA
SA+EA
SA fan speed in event of fire (%)
100
EA fan speed in event of fire (%)
100
Stepless
0-10 V
Stepless
10-0 V
On/off
1-step
On/off
2-step
On/off
3-step binary mode
Inactive
Auto
operation
Cooling
Cooling unit controls
Inactive
Auto
operation
X
X
Stepless
0-10 V
Stepless
10-0 V
On/off
1-step
On/off
2-step
On/off
3-step binary mode