background image

GB.COMPACTAHSK.210520

Registered design. The company reserves the right to make design changes without prior notice.

4     www.swegon.com

2  

GENERAL

2.1 Field of Application

The COMPACT Air and COMPACT Heat units are complete 
air handling units that can be installed directly in the room 
to be ventilated. The ducts for outdoor air and exhaust air 
should be connected to the top of the unit and should be 
arranged to lead out through the wall. Other than that, 
you need only connect the unit to the mains electric sup-
ply. 
The installation work can be carried out very quickly and 
easily and if the task of cutting openings through the wall 
is not complicated, the unit can be operational in just a 
few hours. It is also simple to relocate the air handling 
unit if the nature of the activities conducted in the room 
changes.
The ventilation is very effective thanks to the displacement 
air distribution method used. The built-in control equip-
ment has several functions for economic operation. 
The COMPACT Air and COMPACT Heat units are designed 
for comfort ventilation and can be used in classrooms, day 
nurseries, conference halls, smaller offices, workrooms, 
shops, restaurants and similar public premises.
The difference between the COMPACT Air and the COM-
PACT Heat units is that the COMPACT Heat units can also 
be used for heating. 
It is important keep all the special characteristics of the 
air handling units in mind when planning them into the 
project, installing, adjusting and operating them to fully 
obtain all the benefits the COMPACT system has to offer.
The unit must be installed indoors. 
The COMPACT units are designed and tested for ambient 
temperatures from -25°C to +40°C, and air stream tem-
peratures from -40°C to +40°C. However, for the rotary 
heat exchanger the temperature difference between the 
outdoor air and extract air must not exceed 70°C.

Important!

Always read the safety precautions in Section 1 that 
explain the risks involved in running the unit and 
designate who shall be permitted to operate and 
service the unit, and carefully follow the installation 
instructions provided in each paragraph.

The product identification plates are located inside the 
room unit and on the unit’s rear side. See Sections 2.5.1 
and 2.5.2 respectively.  Refer to the particulars on the 
product identification plate when you contact Swegon. 

2.2 Mechanical Design

The COMPACT is available in one physical size and for two 
airflow ranges. 
Its sheet steel exterior is painted . The decorative strips 
and cover plate around the control display are dark grey, 
NCS S6010-R90B. The inner skin is predominantly made 
of aluminium-zinc plated sheet steel and Magnelis. The 
casing has 30 mm thick intervening mineral wool insula-
tion; the inspection doors have 50 mm thick insulation. 
The COMPACT Air and the COMPACT Heat are equipped 
with pleated, Class ePM1 50% (F7) filters.  
The type RECOnomic rotary heat exchanger is variable 
speed controlled and has a peak temperature efficiency of 
85%.
The supply air and extract air fans are direct-driven plug 
fans. The fans are equipped with EC motors that provide 
high efficiency across the entire operating range. 

2.3 Control System

The IQnomic control system is microprocessor-based and is 
integrated into the unit. It controls and regulates the fans, 
heat exchanger, temperatures, airflows, operating times 
and a large number of internal and external functions as 
well as alarms.

2.4 Environmental Documentation

Environmental Documentation with the Dismantling 
Instructions for recycling and the Environmental Declara-
tion can be downloaded from our home page: wwww.
swegon.com.
The air handling unit is design in such a way that it can 
be dismantled into its natural parts for scrapping. When 
the unit has ended its useful product life, the services of 
an accredited recycling company should be utilized for 
disposal.
Approximately 94% of the parts in COMPACT air handling 
units is recyclable.
Swegon AB is associated with the REPA Register, No. 
5560778465. 
Contact Swegon AB, Phone: +46 (0)512-322 00, if you 
have any questions regarding the dismantling instructions 
or the air handling unit’s impact on the environment.

Содержание COMPACT Air

Страница 1: ...e right to make design changes without prior notice www swegon com 1 OPERATION AND MAINTENANCE INSTRUCTIONS FOR COMPACT AIR COMPACT HEAT Applicable to program version 3 07 and newer versions COMPACT H...

Страница 2: ...tended Operation 29 9 5 3 Summer time Winter time 29 9 6 Heating 30 9 6 1 Heat exchanger 30 9 6 1 1 Defrosting the rotary heat exchanger 30 9 6 1 2 Heating BOOST applies to COMPACT Heat only 31 9 7 Co...

Страница 3: ...ir Handling Unit The air handling unit should normally be started and stopped via the control display Note that the control equipment of the air handling unit is still electrified after the unit has b...

Страница 4: ...nd designate who shall be permitted to operate and service the unit and carefully follow the installation instructions provided in each paragraph The product identification plates are located inside t...

Страница 5: ...n controller 2 Control display on the inspection door 3 Product identification plate 4 Pressure sensor extract air fan 5 Electrical equipm cubicle with control unit 6 VOC sensor 7 Sensor extract air t...

Страница 6: ...act air fan 5 Electrical equipm cubicle with control unit 6 VOC sensor 7 Sensor extract air temperature 8 Extract air filter 9 Electric air heater inside the lower section 10 Sensor supply air tempera...

Страница 7: ...ne so See Section 14 1 4 The air handling unit has a factory setting that makes it ready to operate See Section 21 1 Commissioning Record However in many cases these settings need to be adjusted to su...

Страница 8: ...hted setting Changes are registered immediately and need not be confirmed by pressing Enter INCREASES the value of the highlighted setting Changes are registered immediately and need not be confirmed...

Страница 9: ...DED OPERATION AIRING HEATING HEATING RECIRC NORMAL OPERATION EXTENDED OPERATION AIRING HEATING NORMAL OPERATION EXTENDED OPERATION AIRING HEATING NORMAL OPERATION EXTENDED OPERATION AIRING HEATING EXT...

Страница 10: ...9 2 2 The function can be cancelled by pressing the escape button on the control display and then selecting Normal Operation 5 7 Heating applies to COMPACT Heat only The COMPACT Heat can be used for h...

Страница 11: ...MAN AUTO OP SETTINGS TEMPERATURE FLOW PRESSURE SWITCH CLOCK FILTERS AIR ADJUSTMENT ALARMS INSTALLATION AUTO OPERATION MANUAL LOW SPEED MANUAL HIGH SPEED SWITCH CLOCK TIME DATE TIME CHANNEL YEAR CHANN...

Страница 12: ...nging Operating Mode You can start and stop the air handling unit or change over to manual or automatic operation from the main menu The air handling unit should normally be started and stopped from t...

Страница 13: ...to 15 23 C 20 C extract air temperature The setting range can be changed See Section 14 3 Min Max Setting ERS REGULATION 2 The control unit regulates the relationship between the supply air and extra...

Страница 14: ...an be preset depending on the func tion selected LOW SPEED Must always be preset The value for low fan speed can not be higher than the value for high speed Low speed can be set as 0 which means that...

Страница 15: ...f filter monitoring Calculated filter monitoring preset at factory monitors the fan s speed increase conditional on the degree of fouling in the filter The calibration involves taking airflow and fan...

Страница 16: ...s If an alarm is initiated this is shown in the hand held ter minal both as clear text and by a blinking red diode This menu enables you to read alarms quickly ACTIVE ALARMS Shows alarms that are acti...

Страница 17: ...CHANGE REGULATION SIGNALS IN OUTPUTS IQnomic Plus OPERATION TIME PROGRAMVERSIONS ALARM SETTINGS FIRE ALARM EXTERNAL ALARMS ALARM LIMITS ALARM PRIORITY CONTROL DISPLAY INST LANGUAGE AIR FLOW UNIT MIN M...

Страница 18: ...n the supply airflow is regulated to a lower rate the heat exchanger will have excess heat i e warm extract air giving it capacity to maintain the supply air tempera ture required As the supply airflo...

Страница 19: ...ns are such that the factory preset ERS regulation 1 curve cannot pro vide the results required Conditional on which settings are made it may be necessary to install a post heating coil An individuall...

Страница 20: ...ant s has been indicated during at least 10 minutes Occupant s are no longer present and the preset time period for high speed airflow has expired Conditions that must be met for automatic airing to s...

Страница 21: ...ature should be higher than the preset value The extract air should be at least 2 C warmer than the outdoor air The outdoor temperature should be above the preset value Heating has not been required b...

Страница 22: ...dampers such as shut off dampers for outdoor air and extract air will not be affected These dampers are normally closed when the air handling unit is stopped and they also remain closed The damper in...

Страница 23: ...nder Heating will also change Applies to COMPACT Heat only TEMPERATURE TEMPERATURE REG AIRING FUNCTION SUMMER NIGHT COOL INTERM NIGHT HEAT MORNING BOOST SETPOINT TEMP DISPL HEATING EXT SENSORS Applies...

Страница 24: ...ch must be in Position 0 when the room sensor is used and in Position A when an outdoor sensor is used If the TBLZ 1 24 2 sensor is installed outdoors it must be mounted inside an air tight enclosure...

Страница 25: ...igher power consumption and may also cause discomfort in the form of noise 9 3 1 2 Demand Regulation Control The flow demand is regulated via a 0 10 V input signal from an external sensor such as a ca...

Страница 26: ...g the first energising occasion was not interrupted When the VOC sensor measures contents of emissions impurities that are lower than the preset value the air handling unit s supply air and extract ai...

Страница 27: ...e airflow is demand con trolled The airflow is reduced as a percentage of the current airflow pressure Settings Value Setting Factory range setting Y1 max permissible reduction 0 50 30 X1 breakpoint 3...

Страница 28: ...ptional under Service Level The pressure drop across the filter is continuously moni tored and an alarm will be initiated if the current pressure is greater than the calibration value preset alarm lim...

Страница 29: ...alues are read and set at USER LEVEL The switch clock controls the operating times of the unit The following two basic functions can be set LOW SPEED HIGH SPEED Low speed is the basic level and times...

Страница 30: ...llation instruction for the TBLZ 1 23 aa Pressure sensor The pressure drop across the rotor must then be calibrated to establish a reference pressure drop for monitoring pur poses See Section 7 4 3 Wh...

Страница 31: ...max speed flow The function only works if the air handling unit is operat ing in the extract air regulation mode If demand control or boost is selected in combination with heating boost the flow is c...

Страница 32: ...cooling load exceeds 5 and is de energized when the cooling load is less than 2 Cooling relay 2 is energized when the cooling load exceeds 55 and is de ener gized when the cooling load is less than 50...

Страница 33: ...cannot be combined with pressure regula tion The flow increase takes place between current flow and preset max flow The function can be selected in three variants as follows Comfort The cooling outpu...

Страница 34: ...olling external cooling Cooling output 2 For controlling external cooling Inputs The control unit has two digital outputs terminals 5 6 and 7 8 They must be individually set to the function they are t...

Страница 35: ...gon com 35 INSTALLATION FUNCTIONS FUNCTIONS TEMPERATURE AIR FLOW PRESSURE FILTER OPERATION HEATING COOLING IN OUTPUTS IQnomic Plus ALL YEAR COMFORT 9 9 IQnomic Plus IQnomic Plus is a name given to add...

Страница 36: ...water Y2 C 10 80 C 30 Outdoor temp X3 C 40 40 C 15 Heating water Y3 C 10 80 C 20 Outdoor comp Cool water Active Inactive Inactive Outdoor temp X1 C 40 40 C 10 Cooling water Y1 C 5 30 C 22 Outdoor temp...

Страница 37: ...automatically cali brated This calibration is carried out 3 minutes after the unit has been stopped The text ZERO PT CALIBR is shown in the hand held micro terminal The fans cannot start while calibr...

Страница 38: ...mfort and over load rests totally on the person who activates the function Manual test run can take place for testing the inputs and outputs fans and heat exchanger etc Used when the air handling unit...

Страница 39: ...fire control equipment Manual or automatic resetting of alarms can be selected INTERNAL FIRE ALARM The air handling unit s internal temperature sensors serve as fire protection thermostats An alarm is...

Страница 40: ...settings and activates them when needed The two base settings can be used as a summer setting and as a winter setting of the air handling unit The values in INITIAL SETTING 1 and 2 saved in the intern...

Страница 41: ...configuration is available at www swegon se com under Products Air handling units COMPACT air handling units Documen tation 15 1 EIA 485 Protocol and settings for EIA 485 is specified Settings Value...

Страница 42: ...ary the heat exchanger can be withdrawn from the unit casing and washed with degreasing solvent Only service personnel trained by Swegon shall be permitted to use this cleaning method FABRIC SEAL Lift...

Страница 43: ...f the fault cannot be immediately remedied Consider whether the air handling unit can continue to operate until the fault has been remedied Choose to block the alarm and or to change it from STOP to O...

Страница 44: ...OLLER The air handling unit s control unit cannot establish correct communication with the heat exchanger controller A 1 1 10 s A 10 11 NO COMMUNICATION TO SA FREQUENCY CONV NO COMMUNICATION TO EA FRE...

Страница 45: ...GE IN R HX CONTROLLER Feed voltage 25V is supplied to the rotary heat exchanger s drive motor A 1 1 3 s M 36 OVER VOLTAGE IN R HX CONTROLLER Voltage above the normal level 55 V is supplied to the rota...

Страница 46: ...COMM EA FILTER PRESSURE SENSOR The air handling unit s control unit cannot estab lish correct communication with the supply extract air filter pressure transducer B B 1 1 1 1 10 s 10 s A A 61 NO COMM...

Страница 47: ...rent set point A 1 0 30 m M 108 COOLING WATER TEMP I O 7 ABOVE SET POINT Temperature for cooling water control on I O module is continuously 7 C above its current set point 0 1 0 30 m M 109 HEATING WA...

Страница 48: ...filters was not calibrated after the first start Recurrent at 24 hour inter vals The message will not be received after the pressure across the filters has been calibrated 2 H EXCH CALIBRATION NOT EX...

Страница 49: ...18 60 36 110 810 90 60 639 250 x2 788 4 739 1102 904 1194 16 2114 300 139 196 718 18 60 36 110 810 90 60 639 310 211 228 311 250 x2 20 2 Dimensions COMPACT Heat Overall weight 331 kg Upper section 214...

Страница 50: ...quipment cubicle contains two units the control unit and the power unit The control unit is positioned behind the safety guard of the heat exchanger The safety guard must be dismantled to gain access...

Страница 51: ...ir Temperature sensor extract air Pressure sensor extract air fan Pressure sensor supply air fan Temperature sensor air diffuser section Communication control display PE L N L N PE 201202 3A Power uni...

Страница 52: ...Temperature sensor outdoor air Temperature sensor extract air Pressure sensor extract air fan Pressure sensor supply air fan Temperature sensor air diffuser section Power unit Yellow Green Blue Brown...

Страница 53: ...White 24 V AC out if active 30 31 32 Damper actuator air recirculation damper 30 G0 Black 24 V AC 31 G Red 24 V AC 32 NO White 24 V AC out if active 33 34 35 PWM input for Clean Air Control VOC sensor...

Страница 54: ...0 24 kW Size 03 1 x 230 V 50 60 Hz 0 4 kW The motor controls limit the output power to the value speci fied 20 4 3 Electrical equipment cubicle COMPACT Air One 2 pole 3A Automatic circuit breaker for...

Страница 55: ...ibrated Switch clock current time preset Other control system Switch clock time channel settings Channel Operating mode Times Week day 1 Low High 2 Low High 3 Low High 4 Low High 5 Low High 6 Low High...

Страница 56: ...temp stop C 10 0 SA Setpoint C 10 0 In op time start hh mm 23 00 In op stop hh mm 06 00 Intermittent Night time Heating 1 X Inact Active Inact Active EA Room start C 16 0 EA Room stop C 18 0 SA Night...

Страница 57: ...VOC sensor Ana X Bus Ana Bus VOC low speed 50 VOC high speed 30 Min flow m3 s 0 08 Max flow m3 s 0 2 size 02 or 0 3 size 03 Outdoor temp compensation X Inact Active Inact Active Flow Winter comp Y1 3...

Страница 58: ...tart limit SA temp C 3 0 Ramp time 2 5 Inputs Outputs Relay 1 A Alarm output 4 Relay 2 B Alarm output 4 Input 1 External low speed 5 Input 2 External high speed 5 IQnomic Plus I O Module No 0 Input Ou...

Страница 59: ...nact Active Room temperature C 21 P band C 5 Night blocking Inact Active Inact Active Night comp Heating water X Inact Active Inact Active Temp comp C 2 Night comp Cooling water X Inact Active Inact A...

Страница 60: ...eed 9600 Parity None Stop bit 1 Ethernet Mac Id Individual DHCP server Inactive IP address 10 200 1 1 Port no 80 Net mask 255 0 0 0 GateWay 000 000 000 000 DNS server NO 1 000 000 000 000 NO 2 000 000...

Страница 61: ...No communication SA frequency range gateway A 1 1 21 No communication EA frequency range gateway A 1 1 22 Hall sensor defective SA frequency range A 1 1 23 Hall sensor defective EA frequency range A...

Страница 62: ...B 1 0 71 No communication to I O module No 9 B 1 0 72 No communication to main controller I O A 1 1 85 Cooling Output 1 tripped A 1 0 86 Cooling Output 2 tripped A 1 0 96 Lost settings A 1 1 99 Time l...

Страница 63: ...nits including GOLD E EU regulation 327 2011 all fan data Datum mm kW Actual Req 2015 Actual Req 2015 kW m s Pa min 2 ebm papst 250 ebm papst 0 23 A Static Yes 1 00 65 5 44 4 83 1 62 0 210 0 400 303 2...

Страница 64: ...HSK 210520 Registered design The company reserves the right to make design changes without prior notice 64 www swegon com All documentation is available in digital form and can be downloaded from www...

Отзывы: