Alarm No.:
Function
Factory preset value
Adjusted value
Priority
Indication
Effect
Priority
Indication
Effect
0=blocked
LED
0=Operat. 0=blockedt
LED
0=Operat.
A=A alarm
0=Off
1=Stop
A=A alarm
0=Off
1=Stop
B=B alarm
1=On
B=B alarm
1=On
57
No comm. SA filter pressure sensor
B***
1
0
58
No comm. EA filter pressure sensor
B ***
1
0
61
No comm. r.hx. pressure sensor
B ***
1
0
62
No communication to I/O-module No:0
B ***
1
0
63
No communication to I/O-module No:1
B ***
1
0
64
No communication to I/O-module No:2
B ***
1
0
65
No communication to I/O-module No:3
B ***
1
0
66
No communication to I/O-module No:4
B ***
1
0
67
No communication to I/O-module No:5
B ***
1
0
68
No communication to I/O-module No:6
B ***
1
0
69
No communication to I/O-module No:7
B ***
1
0
70
No communication to I/O-module No:8
B ***
1
0
71
No communication to I/O-module No:9
B ***
1
0
72
No communication to main controller I/O
A
1
1
85
Cooling Output 1 tripped
A
1
0
86
Cooling Output 2 tripped
A
1
0
96
Lost settings
A
1
1
99
Time lock tripped
A
1
1
102 Cooling valve I/O-7 defective
B***
1
0
103 Heating valve I/O-7 defective
A***
1
0
104 Cool. circuit pump I/O-7 tripped
B***
1
0
105 Heat. circuit pump I/O-7 tripped
A***
1
1
106 Cooling water temp. I/O-7 below set point
B***
1
0
107 Heat. water temp. l I/O-7 below set point
A***
1
0
108 Cooling water temp. I/O-7 above set point
0***
1
0
109 Heating water temp. I/O-7 above set point
0***
1
0
110 Cooling water temp. sensor I/0-7 defective
B
1
0
111 Heating water temp. sensor I/0-7 defective
A
1
0
160 No communication VOC sensor
B
1
0
161 Internal comm. error VOC sensor
B
1
0
162 Internal error VOC sensor
B
1
0
163 VOC level below/over alarm limit
B
1
0
* Not adjustable, always stops the air handling unit
** Not adjustable, stops the air handling unit at temperature below +5 °C
*** Blocked if the hand terminal does not display the main menu.
**** Cannot be blocked.
Adjustments carried out by:
Date
Company
Name