GB.COMPACTAHSK.210520
Registered design. The company reserves the right to make design changes without prior notice.
www.swegon.com 31
INSTALLATION
FUNCTIONS
*FUNCTIONS*
TEMPERATURE
AIR FLOW/PRESSURE
FILTER
OPERATION
HEATING
COOLING
IN/OUTPUTS
IQnomic Plus
ALL YEAR COMFORT
9.6.1.2 Heating BOOST
(applies to COMPACT Heat only)
Heating boost means that the air handling unit, operat-
ing in the normal flow regulation mode, increases both
the supply airflow and the extract airflow in order to carry
more heat into the premises.
The fans are allowed to work in the range between cur-
rent flows (low speed, high speed) and preset max speed
flow.
The function only works if the air handling unit is operat-
ing in the extract air regulation mode. If demand control
or boost is selected in combination with heating boost,
the flow is controlled by the function that transmits the
highest output signal to the fans.
A regulated ramp function begins and increases the air-
flow if the temperature exceeds its setpoint and it differs
2-10°C (3°C has been factory preset) to the preset max.
supply air temperature. The control reaction speed (ramp
time = % flow increase/minute) can be set. The highest
possible airflow is limited by the max. flow. For particulars
on setting the max. flow, see Section 7.2.
Settings:
Value
Setting
Factory
range settings
Heating BOOST
Inactive/active Inactive
Start limit
2-10 °C
3 °C
Ramp time
0.5-15%
2.5%
*HEAT*
HEAT EXCHANGER
HEATING BOOST