AMU Rescon
Program List and Explanations
The point of intersection of the tangent with the respective axis will
result in the parameters a and L.
Consult the manual of the control unit for connecting and program
-
ming details. Choose control upwards or downwards.
If Control upwards or Control downwards is active
Setpoint:
User-defined process value (Measured value or flow)
P-Band:
Range below (upwards control) or above (downwards
control) the set-point, within the dosing intensity is reduced from
100% to 0% to reach the set-point without overshooting.
5.2.1.43
Control Parameters:
if Parameter = Meas. value
5.2.1.43.10
Setpoint
: 0.00–200 M
or 0.000–2000
S
5.2.1.43.20
P-Band
: 0.00–200 M
or 0.000–2000
S
5.2.1.43
Control Parameters:
if Parameter = Temperature
5.2.1.43.11
Setpoint
: -30 to +130 °C
5.2.1.43.21
P-Band
: 0 to +100 °C
5.2.1.43
Control Parameters:
if Parameter = Sample Flow
5.2.1.43.12
Setpoint
: 0–200 l/h
5.2.1.43.22
P-Band
: 0–200 l/h
5.2.1.43
Control Parameters:
if Parameter = Meas. uc
5.2.1.43.13
Setpoint
: 0.00–200 M
or 0.000–2000
S
5.2.1.43.23
P-Band
: 0.00–200 M
or 0.000–2000
S
A
B
X
Response to maximum control output
Tangent on the inflection point
Time
Xp
Tn
Tv
= 1.2/a
= 2L
= L/2
X
Y
B
A
L
a