NOTE: DIAGRAMS & ILLUSTRATION ARE NOT TO SCALE.

8

Consult all local codes.

Properly size and route the gas supply line 

from the supply regulator to the area where the 

appliance is to be installed per requirements 

outlined in the National Fuel Gas Code, NFPA 

54 - latest edition (USA) or B149 - latest edition 

(Canada).  Never use galvanized or plastic pipe.   

Gas lines must be routed, constructed and made 

of materials that are in strict accordance with 

local codes and regulations. We recommend 

that a qualified individual such as a plumber 

or gas fitter be hired to correctly size and route 

the gas supply line to the appliance. Installing 

a gas supply line from the fuel supply to the 

appliance involves numerous considerations of 

materials, protection, sizing, locations, controls, 

pressure, sediment, and more. Certainly no one 

unfamiliar and unqualified should attempt sizing 

or installing gas piping.

Remove the gas line access cover plate on either 

the left or right side of the fireplace (see 

Figure 

6

 showing locations).

Install  1/2" min. to 1-1/2" max. inside diameter 

approved gas line through the firebox wall for 

connection to the Vent-Free room heater inside 

the firebox. Connect the gas line before the 

firebox is enclosed in the finished wall. Gas line 

holes and other openings should be caulked with 

high temperature caulk or stuffed with unfaced 

fiberglass insulation.

 

Ensure that a sediment trap is installed in the 

existing gas line, if not, install a sediment trap 

upstream of the heater to prevent moisture and 

contaminants from passing through trap to the 

heater controls and burners. Failure to do so 

could prevent the heater from operating reliably.

An external regulator must be used on all pro-

pane (L.P.G). heaters, in addition to the regulator 

fitted to the heater, to reduce the supply tank 

pressure to 13" W.C. (maximum). Any copper 

tubing used to supply propane (L.P.G). from 

the tank must be internally tinned.

ASSEMBLY STEPS

NOTES:

•   Illustrations shown in this manual reflect 

“typical” installations with nominal dimen-

sions and are for design and framing refer-

ence only. Actual installations may vary due 

to individual design preferences. However, 

always maintain minimum clearances to 

combustible materials and do not violate any 

specific installation requirements. Refer to 

the Framing Specifications 

Figures

 on 

Page 

11. 

•   The following steps represent the normal 

sequence of installation. Each installation 

is unique, however, and might require a 

different sequence.

Step 1.

 Position firebox prior to framing or into 

prepared framing.

Step 2. Field wire the main power supply to 

the appliance if a blower kit is to be installed 

(at the time of installation or a later date).

An optional junction box kit and blower kit is 

required (see 

Page 16  

for ordering information).  

Follow the installation and wiring instructions on 

Pages 12 through 14

).  Electrical connections 

should only be performed by an experienced, 

licensed/certified tradesman.

Step 3.

 Plumb gas line. (Gas connections should 

only be performed by an experienced, licensed/

certified tradesman).

Step 4.

 Install decorative type Vent-Free room 

heater per the instructions provided with the 

Vent-Free room heater.

Step 5.

 Complete finish wall material, sur-

round and optional hearth extension to your 

individual taste.

INSTALLATION

Gas Line Installation

TEST ALL CONNECTIONS FOR GAS LEAKS 

(FACTORY AND FIELD)

Test all gas joints from the gas meter to the gas 

heater regulator for leaks using a

 

gas leak test 

solution (also referred to as bubble leak solution).  

NOTE: 

Using a soapy water solution as a leak 

detection solution is not recommended because 

the soap residue that is left on the pipes/fittings 

can result in a false-positive leak detection reading 

if a gas leak sniffer is used.  Soap residue can also 

result in corrosion over time.

DO NOT USE AN OPEN FLAME TO CHECK 

FOR LEAKS.

 

Leak Test Procedure:

Turn on gas supply and test for gas leaks using 

a gas leak test solution. 

A. Light the appliance (refer to the lighting 

instructions label provided with gas logs).

B. Brush all joints and connections with the gas 

leak detection solution. If bubbles are formed, 

or gas odor is detected, turn the gas control 

knob (off/pilot/on) to the “OFF” position.  Either 

tighten or refasten the leaking connection, then 

retest as described above.

C. When the gas lines are tested and found to 

be leak free, rinse off the leak testing solution 

from gas line fittings.

       

WARNING

Connecting directly to an unregu-

lated propane (L.P.G.) tank can 

cause an explosion.

       

CAUTION

Plumbing connections should 

only be performed by a qualified, 

licensed plumber. Main gas supply 

must be off when plumbing gas line 

to fireplace or performing service.

       

IMPORTANT

Hold heater regulator with a wrench 

to prevent movement when connect-

ing to inlet piping.

       

WARNING

Check Gas Type: The gas supply 

must be the same as stated on the 

heater’s rating plate. If the gas 

supply is different, DO NOT INSTALL 

the heater. Contact your dealer for 

the correct model.

       

IMPORTANT

Pack unfaced fiberglass insulation 

material (not provided) around the 

gas line access hole on appliance 

and all exterior gas line penetra-

tion holes. 

Содержание VRT3132F

Страница 1: ...3132F VRT3136WS VRT3136F VRT3142WS VRT3142F WARNING If the information in this manual is not followed exactly a fire or explosion may resultcausingpropertydamage personalinjury or loss of life FOR USE...

Страница 2: ...perating the heater Installation and repair should be done by a qualified service person The heater should be inspected before use and at least annually by a professional service person More frequent...

Страница 3: ...UCTIONS BEFORE BEGIN NING YOUR INSTALLATION Packaging List Vent Free Gas Firebox Hood Installation and Operation Instructions GENERAL INFORMATION TheseVent Freefireboxenclosuresaredesigned toacceptall...

Страница 4: ...maximum BTU Hr the space can support with the actual amount of BTU Hr used __________ BTU Hr max the space can support __________ BTU Hr actual amount of BTU Hr used Example 61 440 BTU Hr max the spac...

Страница 5: ...ree firebox must be kept clear and free from these combustible materials WARNING Do not use a blower insert heat exchanger insert or other acces sory not approved for use with this appliance WARNING D...

Страница 6: ...bstruct vent openings for heat circulating models NOTE To avoid heat related finish damage we recommend the use of high temperature paint rated 175 F or higher on the underside of the mantel Clearance...

Страница 7: ...ch as carpeting vinyl tile etc a metal or wood barrier covering the entire bottom surface must be used Combustible Mantel and Trim Clearance VRT3100 Series Models WITH Hood Installed Hood is required...

Страница 8: ...ifferent sequence Step 1 Position firebox prior to framing or into prepared framing Step 2 Field wire the main power supply to the appliance if a blower kit is to be installed at the time of installat...

Страница 9: ...hed surface If a wall covering such as drywall is to be attached to the rear wall then the depth must be measured from the drywall surface It is important that this dimension be exact Step 2 Level the...

Страница 10: ...37 1 4 947 23 1 2 597 20 508 3 77 7 3 8 188 15 7 8 404 7 1 2 191 12 305 1 3 8 35 5 1 2 140 30 3 8 772 29 5 8 753 VRT3142WS VRT3142F 42 1067 24 610 47 3 4 1213 37 1 4 947 29 1 2 749 20 508 3 77 7 3 8...

Страница 11: ...creen and rod assemblies see Figure 10 Framing Dimensions Opening VRT3132WS VRT3132F VRT3136WS VRT3136F VRT3142WS VRT3142F A 38 1 4 972 42 1 4 1073 48 1 4 1226 B 40 1 4 1022 40 1 4 1022 40 1 4 1022 C...

Страница 12: ...NG Junction Box Factory Wired Blower Tab Intact Plug blower into this receptacle Ground Green Wall mounted ON OFF Blower Switch or Variable Speed Control Switch Ground HOT SIDE OF RECEPTACLE A ON OFF...

Страница 13: ...igure 16 Step3 Looselytieaknotinthepowercordtotakeupslack seeFigure19 Step 4 Locate the tabs shown in Figure 20 Position the blower assembly so that the tabs located on the cabinet base are seated in...

Страница 14: ...The strain relief bushing not supplied should be pressed into the knock out on J box cover around the Romex thiswillprovideprotectiontothewiresandpreventsstrain against connections from J box See Wir...

Страница 15: ...xtension combustibles allowed No carpet or vinyl Combustible Platform SIDE VIEW Firebox Floor Combustible Wall Figure 23 Raised Hearth Extension Non Combustible Wall see Figure 4 Fireplace Opening Fro...

Страница 16: ...igned to be used when an optional FBK 100 or FBK 200 Blower Kit is to be installed Forced Air Blower Kits Cat No ModelNo Description 80L84 FBK 100 Blower Standard single speed 80L85 FBK 200 Blower Var...

Страница 17: ...e or personal injury NOTE The model and serial number can be found on the rating label located on the bottom left front corner of the appliance If you encounter any problems or have any questions conc...

Страница 18: ..._______________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ___________________...

Страница 19: ...natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard...

Страница 20: ...HP reserves the right to make changes at any time without notice in design materials specifications prices and the discontinuance of colors styles and products Consult your local distributor for firep...

Отзывы: