3 Commissioning
Quick User Manual
26
Action
LCD Display Explanation
Turn off all the household loads.
All the PV power generation
should be exported to the grid, as
shown in the “Correct” figure.
For Reverse Sensor Connection
Make sure that the arrow on the 1-phase sensor must point away from the grid
towards the load. If otherwise, the energy flow indicated on the LCD will be wrong.
Action
LCD Display Explanation
Method 1:
Turn off all the household loads.
All the PV power generation
should be exported to the grid, as
shown in the “Correct” figure.
Method 2:
Stop the inverter via the LCD
menu and turn on the household
loads.
All the load power consumption
should be imported from the grid,
as shown in the “Correct” figure.
The reverse sensor connection will cause the communication fault 084.
To clear the fault 084, please turn off the DC sources and then restart the
system after reconnecting the sensor in correct direction.
Содержание SH5K
Страница 1: ...SH5K QUEN Ver14 201708 Version 1 4 Quick User Manual SH5K Grid Connected Hybrid Inverter ...
Страница 2: ......
Страница 4: ...II System Overview ...
Страница 5: ...III ...
Страница 6: ...IV ...
Страница 7: ...V ...
Страница 8: ...VI ...
Страница 9: ...VII ...
Страница 10: ...VIII ...
Страница 32: ...3 Commissioning Quick User Manual 20 Fig 3 2 Initial Settings ...