Quick User Manual
4 Operation
33
Tab. 4-3
Description of Multi. Stage Protective Parameters
Parameter
Explanation
Max-V prot.
Over-voltage protection
1-V
max
Grid over-voltage 1 (V>)
1-Time
Grid over-voltage 1 (V>) tripping time
2-V
max
Grid over-voltage 2 (V>>)
2-Time
Grid over-voltage 2 (V>>) tripping time
Min-V prot.
Under-voltage protection
1-V
min
Grid under-voltage 1 (V<)
1-Time
Grid under-voltage 1 (V<) tripping time
2-V
min
Grid under–voltage 2 (V<<)
2-Time
Grid under–voltage 2 (V<<) tripping time
Max-F prot.
Over-frequency protection
1-F
max
Grid over-frequency 1 (F>)
1-Time
Grid over-frequency 1 (F>) tripping time
2-F
max
Grid over-frequency 2 (F>>)
2-Time
Grid over-frequency 2 (F>>) tripping time
Min-F prot.
Under-frequency protection
1-F
min
Grid under-frequency 1 (F<)
1-Time
Grid under-frequency 1 (F<) tripping time
2-F
min
Grid under-frequency 2 (F<<)
2-Time
Grid under-frequency 2 (F<<) tripping time
4.5
Setting the Protective Parameters
Main Screen (Press
ENT
)
→
Menu (Press
×
2)
→
Settings (Press
ENT
)
→
Input
password 111 (Press
ENT
)
→
Settings (Press
×9)
→
Prot. Param (Press
ENT
)
When the grid voltage or frequency
reaches the recovery value, the
corresponding fault code displayed on
the LCD will be cleared and the inverter
can start operating.
Power Ramp Rate
:
The ramp up/down rate of power variation.
The power rate limit mode is enabled by default with the
default set-point of 16.67 % of rated power per minute and lies
in the range 5 %–100 %.
Содержание SH5K
Страница 1: ...SH5K QUEN Ver14 201708 Version 1 4 Quick User Manual SH5K Grid Connected Hybrid Inverter ...
Страница 2: ......
Страница 4: ...II System Overview ...
Страница 5: ...III ...
Страница 6: ...IV ...
Страница 7: ...V ...
Страница 8: ...VI ...
Страница 9: ...VII ...
Страница 10: ...VIII ...
Страница 32: ...3 Commissioning Quick User Manual 20 Fig 3 2 Initial Settings ...