SG2K5TL/SG3KTL/SG4KTL-31
User Manual
60
Single-stage Protective Parameter
If the selected protective parameter type is “Single-stage”, the sub-menu will come up.
Press
h
to move cursor right and Press
j
to set the appropriate value. Confirm by
Press ENTER.
If the country code is GB(Great Britain) and protective parameters mode is
“Single-stage”, the output current will be limited to below 16A.
Table 10-3 Single-stage Protective Parameter Explanation
Parameter
Explanation
Vgrid-max Grid
over-voltage value
Vgrid-min
Grid under-voltage value
Fgrid-max
Grid over frequency value
Fgrid-min
Grid under frequency value
Multi-stage Protective Parameter
If the selected protective parameter type is “Multi-stage”, the sub-menu will come up.
Press
►
to move cursor to select the protective stage and press button ENTER to
confirm the selection.
Press
h
to move cursor right and Press
j
to set the appropriate value. Confirm by
Press ENTER.
Table 10-4 Multi-stage Protective Parameter Explanation
Parameter
Explanation
Max-V. prote
Maximum protection voltage
Ⅰ
-Max-V. grid
Stage
Ⅰ
Grid over-voltage
Ⅰ
-Max-V. time
Stage
Ⅰ
Grid over-voltage tripping time
Ⅱ
-Max-V. grid
Stage
Ⅱ
Grid over-voltage
Ⅱ
-Max-V. time
Stage
Ⅱ
Grid over-voltage tripping time
Min-V. prote
Minimum protection voltage
Ⅰ
-Min-V. grid
Stage
Ⅰ
Grid under-voltage
Содержание SG2K5TL
Страница 2: ......
Страница 6: ......
Страница 10: ...IV...
Страница 16: ...SG2K5TL SG3KTL SG4KTL 31 User Manual 6...
Страница 52: ...SG2K5TL SG3KTL SG4KTL 31 User Manual 42 Press the ribbing Pull outwards Disconnect DC connectors...
Страница 60: ...SG2K5TL SG3KTL SG4KTL 31 User Manual 50 10 3 Overview of Complete LCD Menu Fig 10 1 Menu Tree...
Страница 76: ...66 Temperature Derating Curve 1 0 2 45 60 Pnom P U Ambient temperature C...