SG2K5TL/SG3KTL/SG4KTL-31
User Manual
40
−
DC bus starts to charge and check the state of utility grid;
−
If the conditions are OK, inverter feeds AC power to grid and enters into the
running state.
4. Observe state of LED indicators and LCD screen.
If inverter’s commissioning fails, “FAULT” indicator will be lit. And “
State
” on the LCD
screen will display type of malfunction. In this case malfunction must be removed and
then repeat 1 to 4.
If inverter‘s commissioning succeeds, “RUN” indicator will be lit. “
” on the LCD
screen will display “RUN”.