Operation of LCD Menu
10
57
10.13
Auto-test (Only for Italy)
Inverter provides for Italian auto-test operation to verify the validity of functions about
over-voltage protection, under-voltage protection, over-frequency protection and
under-frequency protection.
After confirming “Auto test [Italy]” command, the inverter will perform protection
functions test automatically in turn. Finally the results will come out.
1. Press ENTER to enter general control screen.
2. Press
▼
to navigate arrow-pointer to “Set-param” and then press ENTER.
3. Press
►
to move cursor to the right and press button
▼
to set password 1111.
4. Press ENTER to confirm command.
5. Press
▼
to navigate arrow-pointer to “Sys-param” and then press ENTER.
6. Press
▼
to navigate arrow-pointer to “Auto test [Italy]” and then press ENTER.
Inverter will start to auto testing.
Vgrid-max: the maximum threshold of allowable grid voltage;
Vgrid-min: the minimum threshold of allowable grid voltage;
Fgrid-max: the maximum threshold of allowable grid frequency;
Fgrid-min: the minimum threshold of allowable grid frequency;
Vnorm: current grid voltage; Fnorm: current grid frequency;
Ttrip: time interval from current grid state exceeding allowable ranges to inverter
disconnecting from grid.
If four different values of “Ttrip” meet the corresponding standards, protective
functions of inverter are valid.
Содержание SG2K5TL
Страница 2: ......
Страница 6: ......
Страница 10: ...IV...
Страница 16: ...SG2K5TL SG3KTL SG4KTL 31 User Manual 6...
Страница 52: ...SG2K5TL SG3KTL SG4KTL 31 User Manual 42 Press the ribbing Pull outwards Disconnect DC connectors...
Страница 60: ...SG2K5TL SG3KTL SG4KTL 31 User Manual 50 10 3 Overview of Complete LCD Menu Fig 10 1 Menu Tree...
Страница 76: ...66 Temperature Derating Curve 1 0 2 45 60 Pnom P U Ambient temperature C...
Страница 79: ......