SG2K5TL/SG3KTL/SG4KTL-31
User Manual
58
10.14
Running Parameters Settings
1. Press ENTER to enter general control screen from the default screen.
2. Press
▼
to navigate arrow-pointer to “Set-param” and then press ENTER.
3. Press
►
to move cursor to the right and press button
▼
to set password 1111.
4. Press ENTER to confirm command.
5. Press
▼
to navigate arrow-pointer to “Run-param” and then press ENTER.
6. Press
►
to move right and press
▼
to configure running parameters.
“Standby time” is the time from inverter starting to initialize to inverter feeding power to
grid. This parameter ranges from 10s to 255s. And the default value is 10s.
“Recover time” is the time from the point that the fault is cleared to inverter recovering
to feed power to grid. It ranges from 30s to 300s. And the default value is 30s.
“P-limit”: Power limit ranges from 0 to 100%.
“Save P-limit”: Whether to save up the P-limit value when power down.
“PF”: Power factor ranges from 0.9 to 1 and -0.9 to -1.
“Save PF”: Whether to save up the PF value when power down.