User Manual
61
Inverter
RS485-2
Data Logger
Ethernet
terminal
PC
RS485
terminal
Ethernet port
RS485 cable
Ethernet cable
RS485 Communication of inverter
Inverter
Communication
connection (RS485 bus
connection)
Terminating
Resistor
Single inverter
Only out
No
120ohm
For Multiple Inverters
Where there is more than one inverter, all inverters can be connected in a daisy
chain through an RS485 communication cable. The shielding layer of the RS485
cable should be single-point grounded.
The length of an RS485 communication cable should be less than
1200m.
If several inverters communicate with each other and connect to
the Logger 3000, at most 4 daisy chains are supported and 60
devices in total can be connected (i.e. 4 daisy chains can be
connected with at most 15 devices connected to one chain or 3
daisy chains are connected with at most 20 devices connected to
one chain).