User Manual
45
We provide the socket head cap screw whose matching flat washer
can enhance the fastening function of the nuts.
The maximum permitted temperature for the DC and AC crimping
terminal is 90
℃
(+194
°
F).
6.2
AC Side Cable Connection
6.2.1 AC side requirements
Connection to the utility grid must be done only after receiving
approval from the local utility company.
Before grid-connection, verify to make sure the grid voltage and frequency
meet the requirements of the inverter. Contact the local utility grid company
with any connectivity issues. For detailed parameters, please refer to 11.1
AC Circuit Breaker
An independent circuit breaker is installed outside the output side of the
inverter to ensure that the inverter can be disconnected safely.
Standard Recommended rated voltage Recommended rated current
UL
600V
150A
IEC
690V
160A
The selection of AC circuit breaker should comply with local
standards.
The ultimate short-circuit breaking capacity of the AC circuit
breaker is determined according to on-site transformer
configuration and system solution. If there are any problems,
please contact Sungrow to confirm the technical solution.
It is not allowed to install more than one inverter per fuse or circuit
breaker.