User Manual
33
With an IP65/NEMA 4X protection rating, the
inverter can be installed both outdoors and
indoors.
To achieve better running effect
.
The ambient
temperature should be within -25
℃
…60
℃
(-13°F to 140°F). The inverter will operate with
power derating if the temperature is too high.
The relative humidity range of the installation
site is 0-100%.
Max. ambient
temperature:
60
℃
(
+140°F)
Min. ambient
temperature:
-25
℃
(-13°F)
Relative
humidity:
0-100%
Ensure there is enough space for convection (The fans are maintained on the
left side of the inverter, and a larger clearance is required.)
Cool air
Hot air
≥
400mm
(15.7inch)
≥
450
mm
(17
.7inch
)
Ground
≥
400mm
(15.7inch)
When installing multiple inverters, it is recommended to install multiple
devices side by side.
≥
400mm
(15.7inch)
≥
600mm
(23.6inch)
≥
600mm
(23.6inch)
≥
600mm
(23.6inch)
Side by side installation (Recommended)
在环境温度为
-25
℃
~45
℃时,可以采用上下叠加和交错安装的方式。