User Manual
48
L 1
L 2
L 3
M1
M2
M3
M4
500V
500V
500V
750V
Fig. 6-3
The schematic diagram of AC SPD
6.2.2 Grid Connection
The AC terminal block is on the bottom of the inverter. AC connection is the
three-phase-three-wire grid +PE connection (L1, L2, L3 and PE).
AC Cable Requirements
Select AC cables according to the following factors:
Grid impedance complies with the specifications below to avoid accidental
shortcircuit or output power derating.
600
615
630
645
660
675
690
0
0.15
Max
. grid impedance
(Ohm
)
AC voltage without loads (V)
0.3
0.45
0.6
0.43
Considering the voltage drop and other conditions, please enlarge the cable
dimension. Power loss of the cable should be less than 1% of the nominal
power.
Withstand ambient temperature.
Cable layout and installation conditions (inside wall, underground, free air,
etc.)