10 Operation of LCD Display Panel
User Manual
78
Confirm settings by pressing
ENTER
and enter the
“Setting confirmation” screen.
Check all above-mentioned parameter settings. Confirm
them by pressing
ENTER
. Cancel by pressing
ESC
and
reset.
When the Country or the Grid code or LVRT switch mode is changed, the
protective settings will be unavailable unless the inverter is re-energized.
10.12
Communication Parameters Setting
Main Screen(Press
ENTER
)
→
Menu screen(Press
j
×
3)
→
Set-param
(Press
ENTER
)
→
Enter password(Press
ENTER
, Press
j
×
3 )
→
Com-param
(Press
ENTER
)
Press
h
to move cursor right and
Press
j
to set the
appropriate value. Confirm settings by Pressing
ENTER
.
The range of communication address is 1...247.
10.13
PV Configuration Mode Setting
Main Screen(Press
ENTER
)
→
Menu screen(Press
j
×
3)
→
Set-param
(Press
ENTER
)
→
Enter password(Press
ENTER
, Press
j
×
4 )
→
PV config
mode (Press
ENTER
)
→
Enter password(111111, Press
ENTER
)
On the “PV config mode” screen, Press
j
to choose PV
configuration mode, Press
ENTER
to confirm the
settings.
PV configuration mode will be valid when the inverter
is re-energized again by rotating DC switch to the
“OFF” position and then to the “ON” position.
The default configuration mode is independent
mode.