6 Electrical Connection
User Manual
28
Fig. 6-1
Terminals Description
Item
Description
1
AC: AC terminals
SG10KTL/SG12KTL/SG15KTL: Amphenol C16_L; SG20KTL: Wieland RST50I5
2
RS485 IN / RS485 OUT: RS485communication terminals, RJ45
3
DC1/DC2: DC terminals, MC4 PV-KST4/6II-UR, PV-KBT4/6II-UR
4
Integrated DC switch
5
Second Protective Earth Terminals
6.2
Simplified Electrical Connection Diagram
Connecting inverter to the existing PV system includes connecting inverter to local
grid and connecting inverter to PV arrays. There may be communication connection
for monitoring inverter operation if necessary.
All electrical connection should follow the National Wiring Rules of Standard AS/NZS
3000. The requirements in AS 4777.1 and AS/NZS 3000 indicate that a DC isolator
must be used before the inverter.