10 Operation of LCD Display Panel
User Manual
76
Confirm by pressing
ENTER
after country code selection.
Choose grid code according to actual grid condition.
Note: “LV” represents Low Voltage Grid Code, and “MV”
represents Middle Voltage Grid Code.
When choose MV,
Press
h
to enter the LVRT function
selection,
Press
j
to switch on or off the LVRT function
and
Press
ENTER
to confirm the selection.
Note:
If the Country selected does not have the “Grid
codes” directives, this configuration will not affect the
following procedures.
However, you may select the MV to enable/disable the
LVRT function regardless of the country selected.
Press
j
to select protective parameter type. Press
ENTER
to confirm the selection.
If the country selection is “IT” (Italy), the Pro-param menu
right will show, refer to the 10.14.3 Protective Parameters
Setting for Italy for detailed settings.
Single-stage Protective Parameters (when the country selection is not “IT”)
If the selected protective parameter type is “Single-stage”,
the following sub-menu will come up.
Press
j
to select parameter,
Press
h
to move cursor right
and
Press
j
to set the appropriate value. Confirm settings
by Pressing
ENTER
.
Tab. 10-7
Single-stage Protective Parameters Explanation
Parameter
Explanation
Max-V.grid
Grid over-voltage value
Min-V.grid Grid
under-voltage
value
Max-Fgrid
Grid over frequency value
Min-F.grid
Grid under frequency value