Chapter 2
Installing the Library
13
shows the floor space requirements for the rackmount library.
FIGURE 2-2
Floor Space Requirements (Rackmount Library)
Floor Clearance
The stand-alone version of the library has a nominal floor clearance of 0.75 inch
(1.9 cm). Place the library on a level, uncarpeted floor free of cracks, depressions,
and other similar defects.
Floor Strength and Inclination
The floor in the installation site must be rated at 250 lb/ft
2
(1221 kg/m
2
). This is
sufficient to support a fully loaded library on the floor or in a rack.
The floor in the installation site must also be level to within 0.25 inch (6.4 mm) over
a 6-foot-by-6-foot (1.8 m by 1.8 m) area.
17.5 in.
(45 cm)
24 in.
(61 cm)
Library
30 in.
(76.2 cm)
24 in.
(61 cm) each side
NOTE: When extended out of the rack (as shown),
the library should have 24 inches (61 cm) of
clearance overhead, in front and on each side.
24 in.
(61 cm)
(extended from
rack)
19-inch rack
The library requires no side clearance inside
the rack.
Содержание StorEdge L1000
Страница 16: ...xvi Sun StorEdge L1000 User s Guide May 1998 ...
Страница 18: ...xviii Sun StorEdge L1000 User s Guide May 1998 ...
Страница 58: ...36 Sun StorEdge L1000 User s Guide May 1998 ...
Страница 72: ...50 Sun StorEdge L1000 User s Guide May 1998 ...
Страница 94: ...72 Sun StorEdge L1000 User s Guide May 1998 ...
Страница 100: ...78 Sun StorEdge L1000 User s Guide May 1998 ...
Страница 104: ...82 Sun StorEdge L1000 User s Guide May 1998 ...
Страница 122: ...100 Sun StorEdge L1000 User s Guide May 1998 ...