Chapter 5
Removing and Replacing Miscellaneous Internal Components
75
1. Prepare the server for servicing, if you have not done so already:
a. Power off the server.
See
“Powering Off the Server” on page
b. Remove the server cover.
See
“Removing the Server Cover” on page
c. Close the rotating service module.
See
“Opening the Rotating Service Module” on page
d. Ensure that the server is properly grounded.
See
“Avoiding Electrostatic Discharge” on page
e. Rotate the air duct and rear fan assembly up.
See
“Removing or Rotating the Air Duct and Rear Fan Assembly” on page
.
Note that you only have to rotate the assembly up, not remove it from the server.
2. Locate the correct memory socket (
3. Ensure that the socket latches are open.
4. Press the memory module in the memory socket.
5. Press down until the socket latches snap into place.
6. Close the air duct and rear fan assembly.
See
“Installing or Closing the Air Duct and Rear Fan Assembly” on page
7. Close the rotating service module.
See
“Closing the Rotating Service Module” on page
.
8. Install the server cover.
See
“Installing the Server Cover” on page
9. Power on the server.
See
Содержание Netra 240
Страница 7: ...Contents vii Index 133...
Страница 8: ...viii Netra 240 Server Service Manual June 2004...
Страница 12: ...xii Netra 240 Server Service Manual June 2004...
Страница 70: ...52 Netra 240 Server Service Manual June 2004...
Страница 84: ...66 Netra 240 Server Service Manual June 2004...
Страница 120: ...102 Netra 240 Server Service Manual June 2004...
Страница 124: ...106 Netra 240 Server Service Manual June 2004...
Страница 132: ...114 Netra 240 Server Service Manual June 2004...