S1 and S2 Self-regulating Heating Cable Maximum Circuit Lengths in Feet
Model
Number
Operating
Voltage
Design Load
(Amps/foot) @0
E
Start-up
Temp
Circuit Breaker Size
15A
20A
30A
40A
S1
120 Vac
20
E
F.
100
135
175
175
0.155
0
E
F.
80
105
155
175
S2
208 Vac
20
E
F.
185
245
350
350
0.083
0
E
F.
145
190
290
350
S2
240 Vac
20
E
F.
190
250
350
350
0.080
0
E
F.
150
200
295
350
S2
277 Vac
20
E
F.
195
255
350
350
0.077
0
E
F.
155
205
310
350
WARNING: The Radiant Edge ice melt system
MUST
be protected with a
ground fault protection device per local codes and the NEC (National
Electric Code) and CSA (Canadian Standards Association).