16
Hyponic®
Operating and Maintenance Manual
Hyponic® Operating and Maintenance Manual
17
www.SumitomoDrive.com
Motor Operating Precautions
Table 6. Varistor Specification Table
Operating Voltage
190-230V
380-460V
575V
Varistor Rated Voltage
AC260-300V
AC510V
AC604V
Varistor Voltage
430-470V
820V
1000V
Rated Watt
FB-01A1, 02A1, 05A1
Over 0.4W
Over 0.4W
Over 0.4W
FB-1E, 1D
Over 0.6W
Over 0.6W
Over 0.4W
FB-1HE, 2E, 2D, 3E
Over 1.5W
Over 1.5W
Over 0.6W
FB-5E, 8E, 10E, 15E
Over 1.5W
Over 1.5W
Over 1.5W
Fig.14-a Normal Brake Action, 230V or 575V Brake
Fig. 14-b Fast Brake Action, 230V Brake
Fig. 14-c Normal Brake Action, 460V Brake
Fig. 14-d Fast Brake Action, 460V or 575V Brake
Wiring Connections for VFD (Inverter)
Models FB-01A1 through FB-15E, 230/460V, 60Hz or 575V, 60Hz
VFD
VFD
VFD
VFD
VFD
VFD
VFD
VFD
a.
Always ground the motor terminal box or frame
.
b.
Insulation Resistance
Follow instructions supplied with the motor insulation tester. The insulation resistance value will vary depending on
the temperature, humidity, extent of contamination, the servicing period, test running time, as well as the motor out-
put, voltage and type of insulation. Therefore, the insulation resistance (r) cannot be expressed uniformly; however, it
should be equal to or greater than the value listed in
Table 7
.
Motor Voltage
Megger Voltage
Insulation Resistance (r)
Low voltage motor (≤ 600V)
500V
Higher than 1 M
Ω
Table 7. Insulation Resistance
Key:
VR:
Varistor (protective device, refer to Varistor Specification
Table 6
)