Section 2
SUPERVISOR
II
DESCRIPTION
9
S
FULL LD --- Machine is running and fully
loaded. This state is only displayed if the
machine has a full load valve.
S
RMT STOP --- Compressor is off but
armed to start. The machine will start when
the remote start contact is closed. NOTE :
the machine may start at any time.
S
SEQ STOP --- Compressor is off but armed
to start. The machine will start when the se-
quencing conditions meet the critera to
start. NOTE : the machine may start at any
time.
This default display appears as follows:
STOP
110 180
If there are alarms active they will alternately be
shown with the default display. The machine status
will be displayed for 2 seconds then the alarms for 2
seconds each. For example:
T1 HI
110 180
To view other status press the DISPLY key. All tem-
peratures and pressures may be displayed as well
as other status information. To scroll through the
displays press the up arrow or down arrow keys.
Up arrow moves to the next display, down arrow
the previous display. To return to the default dispaly
press the display key.
S
Separator differential pressure and the
maximum limit. If the limit is exceeded, a
separator maintenance warning will be dis-
played.
dP 1 4
MAX 10
S
Sump pressure and line pressure.
P1 113
P2 108
S
Oil filter differential pressure and the maxi-
mum limit. If the limit is exceeded oil main-
tenance warning will be displayed.
dP2 4
MAX 20
S
Pressure before (P4) and after (P3) oil filter.
P3 108
P4 113
S
Oil differential pressure and the minimum
limit. If the pressure goes below the limit a
P3 LOW shutdown will occur. Oil differential
(dP3) is defined as P3---P½
dP3 40
MIN 1
S
Unit discharge temperature and the maxi-
mum limit. If the temperature exceeds the
limit a T1 HI shutdown will occur.
T1 210
MAX 235
S
Dry side discharge temperature and the
maximum limit. If the temperature exceeds
the limit a T2 HI shutdown will occur.
T2 210
MAX 235
S
Oil temperature and the maximum limit.
If the temperature exceeds the limit a T3 HI
shutdown will occur.
T3 210
MAX 235
S
Interstage temperature and the maximum
limit. If the temperature exceeds the limit a
T4 HI shutdown will occur.
T4 210
MAX 235
S
Total hours that the compressor has been
running.
HRS RUN
001234.0
S
Total hours that the compressor has been
loaded.
HRS LOAD
000987.0
Содержание Supervisor II
Страница 1: ...SUPERVISOR Part Number 02250071 398 eSullair Corporation INSTRUCTION MANUAL II ALL MODELS ...
Страница 6: ...Section 1 SAFETY 2 Figure 1 1 Decals ...
Страница 7: ...Section 2 SUPERVISOR II DESCRIPTION 3 Figure 2 1 Supervisor II Panel All Models Except DS 13 ...
Страница 8: ...Section 2 SUPERVISOR II DESCRIPTION 4 Figure 2 1A Supervisor Panel DS 13 ...
Страница 18: ...14 NOTES ...
Страница 22: ...18 NOTES ...
Страница 24: ...20 NOTES ...