Section 5
MAINTENANCE AND TROUBLESHOOTING
22
5.4A --- ES---8 TROUBLESHOOTING (Continued)
SYMPTOM
PROBABLE CAUSE
REMEDY
P1 HI Message
P1 MAX --- 3psi (.2 bar) Exceeded for
Pre---Alarm
P1 MAX Exceeded for Shutdown
Discharge Pressure Exceeded
Shutdown Level Because:
Unloading Device (i.e, Blowdown
Check operation of unloading device.
Valve, Sullicon Actuator, Optional
Spiral Valve) Failed to Operate
Pressure Regulator Maladjusted
Check operation of pressure regulator.
Solenoid Valve Failed
Check operation of solenoid valve.
to Operate
Control Air Signal Leaks
Check tubework feeding control
signal for leaks.
Control Air Signal Filter Clogged
See compressor Operator’s Manual for filter
assembly service.
SEP MNTN Message
Plugged Separator
Replace separator elements.
dP1 > 10 PSI (0.7 bar)
Check P1 & P2 pressure transducers.
COMPRESSOR DOES NOT
BUILD FULL DISCHARGE
PRESSURE
Air Demand Exceeds Supply
Check air service lines for open
valves or leaks.
Inlet Air Filter Clogged
Check for maintenance message
on Supervisor
II
display. Inspect and/or
change element.
Inlet Valve Not Fully Open
Check actuation and butterfly disc
position.
Pressure Sensor and/or Connections
Check connections from transducer.
at Fault
If adequate, replace transducer.
LINE PRESSURE RISES ABOVE
UNLOAD SETTING
Pressure Sensor P2 at Fault
Check connections from trans---
ducer. If adequate, replace
transducer.
Unloading Device (i.e., Blowdown
Check operation of unloading device.
Valve, Sullicon Actuator, Optional
Spiral Valve) Failed to Operate
LINE PRESSURE RISES ABOVE
UNLOAD SETTING
Solenoid Valve Failed
Check operation of solenoid
to Operate
valve.
Control Air Signal Leaks
Check tubework feeding control
signal for leaks.
Control Air Signal Filter Clogged
See compressor Operator’s Manual for filter
assembly service.
EXCESSIVE FLUID CONSUMPTION
Clogged Return Line Strainer or
Clean strainer --- screen and o---ring
Orifice
replacement kit available. Clean
orifice.
Damaged or Improperly Gasketed
Inspect separator elements and
Separator Elements
gaskets. Replace if damaged.
Fluid System Leaks
Check tube/pipework for leaks.
Fluid Level Too High
Drain excess fluid.
Excessive Fluid Foaming
Drain and change fluid.
Содержание Supervisor II
Страница 1: ...SUPERVISOR Part Number 02250071 398 eSullair Corporation INSTRUCTION MANUAL II ALL MODELS ...
Страница 6: ...Section 1 SAFETY 2 Figure 1 1 Decals ...
Страница 7: ...Section 2 SUPERVISOR II DESCRIPTION 3 Figure 2 1 Supervisor II Panel All Models Except DS 13 ...
Страница 8: ...Section 2 SUPERVISOR II DESCRIPTION 4 Figure 2 1A Supervisor Panel DS 13 ...
Страница 18: ...14 NOTES ...
Страница 22: ...18 NOTES ...
Страница 24: ...20 NOTES ...