SECTION 2

SUPERVISOR CONTROLLER™ USER MANUAL

 

9

right arrow keys to move to the letter to be changed,
then use the up and down arrow to change the letter.
Push the enter key to complete the edit. The
following are detailed descriptions of the various
displays. 

2.4

STATUS—CURRENT 

PRESSURES, 

TEMPERATURES, INPUTS 

AND OUTPUTS 

All inputs and outputs are displayed showing both the
designator and the description (eg. T1- Discharge)
along with the selected temperature (C or F) or
pressure (psi, bar, kPa) units. Digital inputs and
outputs are shown either as a ‘0’ (zero) or ‘1’ (one).
Zero is off and one is on. This is a view only display. 

The order of display is : 

Temperatures

—T1 through T4 depending on model. 

Pressures

—P1 through P4 depending on model. 

Delta pressures

—dp1 through dp3 depending on

model. 

Load Hours

—Hours machine has run loaded. 

Run Hours

—Hours machine has run loaded or

unloaded. 

Load Cycles—

Number of load/unload cycles. 

Starts

—Number of times machine has started. 

E-Stop String

—E-Stop push button. 

Aux E-Stop

—Auxiliary E-Stop, wired by customer. 

Digital Inputs

—D1 through D10, depending on

model. 

Relay Outputs

—K1 through K8, depending on

model. 

2.5

CONTROL PARAMETERS—

PRESSURE, TEMPERATURE 

AND TIMER SETTINGS 

Parameters that control the operation of the machine
are viewed and set using this display. These
parameters may vary by machine model. 

The Control Parameters are : 

Unload pressure

—The pressure where the machine

is unloaded. For example if this parameter is set to
110 psi (7.6 bar) the machine will unload when the
line pressure is above 110 psi (7.6 bar). 

Load delta

—The pressure differential below the

unload pressure where the machine is loaded. For
example if the unload pressure is set to 110 psi (7.6
bar) and the load differential is set to 10 psid (0.7
bar), the machine will load when the line pressure
goes below 100 psi (6.9 bar). 

Setpoint

—(VSD packages only) The targeted

pressure for the variable speed controls. This is
normally adjusted near the bottom of the load/unload
band above. The speed will be adjusted to maintain
this pressure. Refer to 

Section 6

 for additional

details. 

Unload Time

—If the machine is running in AUTO

mode, this parameter specifies the amount of time
that the machine will run unloaded before shutting
off. If the time is set less than 15 minutes (for
example 5), there may be times when the machine
will run unloaded for more than 15 minutes. This is
because there is another timer that keeps the
machine from being started more than four times an
hour. This secondary timer is disabled when a
machine is configured for VSD motor control. 

Drain Interval

—If the machine has an electric

solenoid drain, this parameter and the following
parameter (Drain Time) are used to turn on the drain.
The interval is the time between activations of the
drain and the Drain Time is the length of the time
energized. This does not apply to the Sullair SCD
zero loss drain, which is not controlled or monitored
by the Supervisor. 

Drain Time—

Length of time that drain is energized. 

Restart time—

Time to wait after power up before starting machine.
This parameter is used to keep several machines
from starting at the same time after power up, or to
delay start until other equipment is started. If
disabled parameter is zero, the machine will not
automatically start after power up. If this parameter is
a number larger than zero, the machine restarts after
a delay defined by this time. For example, if the

 WARNING

Enabling this function also enables auto-
matic restart after power recovery. Be sure 
to depress the Emergency Stop button to 
defeat this function when automatic start is 
to be prevented.

Содержание SUPERVISOR CONTROLLER

Страница 1: ...VOID its warranty WARRANTY NOTICE PART NUMBER KEEP FOR FUTURE REFERENCE USER MANUAL SULLAIR CORPORATION The information in this manual is current as of its publication date and applies to compressor s...

Страница 2: ...d at Michigan City Indiana Instruction includes training on the function and installation of Sullair service parts troubleshooting common faults and malfunctions and actual equipment operation These s...

Страница 3: ...REVENTIVE MAINTENANCE INFORMATION AND TIMERS 10 2 7 FAULT LOG LOG OF PREVIOUS FAULTS 10 2 8 SENSOR LOG 10 2 9 SEQUENCING SEQUENCING COMMUNICATION PARAMETERS 11 2 10 SYSTEM DISPLAY DISPLAY OF MODES OF...

Страница 4: ...EED DRIVE 33 6 1 SAFETY 34 6 2 OVERVIEW 36 6 3 INSTALLATION 36 6 4 SUPERVISOR DISPLAY AND MENUS 37 6 5 STARTUP OF NEW COMPRESSOR PACKAGE 38 6 6 FAULT AND WARNING CODES 41 6 7 COMMISSIONING YOUR VSD 41...

Страница 5: ...y statements contained herein are applicable to most compressors and the concepts behind these statements are generally applicable to all compressors 1 2 PERSONAL PROTECTIVE EQUIPMENT A Prior to insta...

Страница 6: ...ntains several decals which contain necessary information for safe performance These decals should never be removed If a decal becomes damaged contact your nearest Sullair Department for replacement p...

Страница 7: ...NOTE 1 250017 903 1 decal warning auto start 2 250027 935 1 decal danger breath air I 3 250003 144 1 sign warning food grade lube 4 041065 1 decal auto start I OSHA and FDA guidelines are superseded...

Страница 8: ...NOTES 6...

Страница 9: ...following seven keys Help key used to display possible causes of and correction for an alarm or fault Returns to main display Used to edit text or numbers move cursor left Used to edit text or numbers...

Страница 10: ...nt pressures temperatures inputs and outputs VSD Satus VSD packages only See Section 6 Control Parameters Pressure and temperature and timer settings Maintenance Preventive maintenance information and...

Страница 11: ...bar and the load differential is set to 10 psid 0 7 bar the machine will load when the line pressure goes below 100 psi 6 9 bar Setpoint VSD packages only The targeted pressure for the variable speed...

Страница 12: ...ry air filter part number Oil hours Hours before oil change PN Oil part number Oil Anal Hours before oil analysis These hours and part numbers can be changed using the enter and arrow keys 2 7 FAULT L...

Страница 13: ...e other machines For example in a two machine system with Rotate set at 100 hrs The machine that is running will shut off when the Seq Hrs are 100 more that the machine that is stopped Minute Hour Day...

Страница 14: ...aximum discharge pressure KT Fluid Yes or No indicating fluid Water Switch Water pressure switch Yes or No Oil Switch Oil pressure differential switch Yes or No Min Load Psi Minimum acceptable load P1...

Страница 15: ...13 NOTES...

Страница 16: ...SUPERVISOR CONTROLLER USER MANUAL SECTION 2 14 Table 2 1 Supervisor Controller Menu Tree...

Страница 17: ...rocedure should be used to make the initial start up of the compressor 1 Be sure that all preparations and checks described in the Installation Section have been made 2 Read the preceding pages of thi...

Страница 18: ...16 NOTES...

Страница 19: ...blem persist after making the recommended check consult your nearest Sullair Distributor or the Sullair Corporation factory Service Department NOTE Whereas Section 4 1 and Section 4 2 por tray common...

Страница 20: ...set below limit of compres sor Check motor starter contacts for proper operation Check line voltage if low consult power company I O Mod Com Error Com Mod Com Error Motor Mod Com Error VSD Com Error...

Страница 21: ...P1 Separator High FLOODED ALWAYS Pressure Across Separa tor High Plugged separator elements replace Pressure sensor failure check sensor wiring Factory Setup Error ALL ALWAYS The Factory Setup Infor m...

Страница 22: ...ion ALL ALWAYS Cooler fins dirty clean fins and fan Water cooled Low water flow check for valve closed pump off or broken pipe Water cooled High water temperature increase flow or lower water temperat...

Страница 23: ...iring to drive VSD Param Lim Fault ALL VSD Communication Error at Powerup or Setup Check control wiring to drive Incorrect Factory or VSD Setup Check setup menus and drive rating VSD Drive Fault__ ALL...

Страница 24: ...tly Delayed for temp spikes T_1 High Fault 245 0 0 Constantly Immediate Warning T_1 High Fault 255 0 0 Constantly Immediate Fault T_1 High Fault 500 0 0 Constantly Sensor failure fault T_2 Low Fault 4...

Страница 25: ...onstantly Sensor failure fault T_2 High Warn 245 5 30 Constantly Delayed for temp spikes T_2 HIgh Warn 255 0 0 Constantly Immediate Warning T_2 High Fault 255 5 30 Constantly Delayed for temp spikes T...

Страница 26: ...etup Always 0 0 30 Stop Timer If not 0 run unloaded for this time before stopping Setup Always 0 0 30 Lube Cycle Prelube Postlube time Setup Always 0 0 2 K8 Option Disable Lube Pump Master Control Set...

Страница 27: ...ye to delta starter transition time Seconds User Always 0 0 2 Language French German Italian Spanish English User Always 0 0 1 Temp Units Fahrenheit Celsius User Always 0 0 2 Press Units Pressure unit...

Страница 28: ...the Restart Timer has a value other than zero If the Restart Timer is zero then the machine always powers up in Manual Stop 4 3 REMOTE STOP START INPUT Table 4 6 describes how a machine reacts to the...

Страница 29: ...delay P2 Load psi P1 5 psig Remote Remote Off Cont Remote Stop Remote Remote Off Auto Remote Stop Remote Remote On Cont Start after Restart delay Remote Remote On Auto Start after Restart delay P2 Lo...

Страница 30: ...28 NOTES...

Страница 31: ...Section 5 29 SUPERVISOR CONTROLLER USER MANUAL WIRING DIAGRAMS...

Страница 32: ...SUPERVISOR CONTROLLER USER MANUAL SECTION 5 30 Figure 5 1 WIRING DIAGRAM SUPERVISOR COMMUNICATION MODULE 02250131 248 R05...

Страница 33: ...2009 02250132 198 R04 NOTES 1 DASHED LINES INDICATE TYPICAL FIELD CONNECTIONS THAT VARY DEPENDING ON COMPRESSOR BEING RETROFITTED AND IS FIELD WIRED FACTORY WIRING IS SOLID 2 DISPLAY E STOP CONNECTIO...

Страница 34: ...THAT VARY DEPENDING ON COMPRESSOR BEING RETROFITTED AND IS FIELD WIRED FACTORY WIRING IS SOLID 2 DISPLAY E STOP CONNECTION IS WIRED TO TERMINAL BLOCK INSIDE REAR COVER OF DISPLAY 3 CHASSIS GROUND WIR...

Страница 35: ...o the variable speed drive make sure that the front and cable covers are closed and fastened to prevent exposure to potential electrical fault condi tions Failure to observe this precaution could resu...

Страница 36: ...ing a multimeter set to measure DC voltage Failure to follow the above precautions may cause death or severe injury CAUTION Do not perform any meggar or voltage with stand tests on any part of the var...

Страница 37: ...590 6x350 2x500 500 2x400 400 Table 6 2 Conductor and Fuse Sizes 575V HP Size A Fuse A Wire Size Power 75o C Rated Wire Wire Size Ground Wire Size Power 90o C Rated Wire Wire Size Ground 15 18 30 10 1...

Страница 38: ...rmance See Section 6 4 2 for reset procedure Capacity Average delivery in CFM Capacity Average percent of full package capacity Power Average total package power in KW Power Average percent of power a...

Страница 39: ...adjustments sets up the parameters of the drive for the construction of the compressor package These may be viewed at any time but are protected by the password in the Factory Setup group VSD Auto Set...

Страница 40: ...display these as Drive Fault with a code number If a keypad service tool is plugged into the drive it will display the fault code and the fault name shown in the first two columns Code Fault Possible...

Страница 41: ...upply voltage If it was within specification at the time of the fault an internal failure has occurred Contact Sullair service 10 Input line supervision Input line phase is low or missing Check the ut...

Страница 42: ...protection has detected a high short term overload current Check loading Check motor size 32 Fan cooling The variable speed drive cooling fan did not start when com manded Contact Sullair service 36 C...

Страница 43: ...rvisor Controller VSD Status Drive Temp Following all proper safety precautions check or perform the following 1 Using clean dry compressed air to clean the unit of all dust and debris 2 Check all con...

Страница 44: ...driver and pushing in on the two side tabs then pull up The fan needs to be removed with caution so the electrical connections are not damaged 5 Clean the fan of dirt and debris or install a new fan a...

Страница 45: ...e machine if necessary FAN REMOVAL AND REPLACEMENT 50 60HP 480V 1 Remove front cover of VSD 2 Remove incoming power lead motor leads and communication wire to VSD 3 You will need to remove the VSD fro...

Страница 46: ...und fan connectors from the VSD B 7 Push the wires though the hole in VSD HEAT SINK CLEANING 75HP 125HP 480V 1 Remove VSD from machine 2 Remove fan This will give you the area that the heat sinks and...

Страница 47: ...ide cov ers 2 See pictures at right 3 Remove incoming power lead motor leads and communication wire to VSD 4 In order to remove fan from VSD Remove the two front screws from each fan in the pic ture b...

Страница 48: ...tions on how to care for the VSD filter VSD FILTER CLEANING 1 Locate the VSD filter from the following fig ures 2 Remove the filter from the assembly The filters are magnetic and should pull off easil...

Страница 49: ...SECTION 6 SUPERVISOR CONTROLLER USER MANUAL 47 VSD FILTER DRAWING V200TS FILTER ELEMENT Figure 6 2 V200TS...

Страница 50: ...CONTROLLER USER MANUAL SECTION 6 48 INSTALL THE FILTER ELEMENT ON THE UNDERSIDE OF THE MOUNTING PLATFORM ON THE FRAME THE FILTER IS TO COVER THE AIR OPENING TO THE VSD VSD FILTER DRAWING V200TS Figure...

Страница 51: ...NOTES...

Страница 52: ...U S A Specifications subject to change without prior notice E12EP Always air Always there SULLAIR CORPORATION 3700 East Michigan Boulevard Michigan City Indiana 46360 U S A Telephone 1 219 879 5451 W...

Отзывы: